| 2019-04-24 08:12:44 | GAS 1ST REVIEW**DENIED** |
| | |
| | 1) PLANS/ SUBMITTAL DOCUMENTS THAT BEAR THE NAME, TITLE |
| | BLOCK AND OR LICENSE NUMBER OF A DESIGN PROFESSIONAL |
| | SHALL BE WET SIGNED AND SEAL. FAC 61G15-23.001. FL ST |
| | 471,481. ALL OTHER PLANS/ SUBMITTAL DOCS SHALL BE |
| | SIGNED AND DATE MY PERSON TAKING RESPONSIBILITY. |
| | |
| | 2) WHAT PIPING SIZE AND MATERIAL IS ABOVEGROUND? SHOW |
| | THE TYPE OF ALL PIPE MATERIAL BEING INSTALLED, ALL PIPE |
| | SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 3)SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| | REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION. |
| | 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| | |
| | 4)AT SOME POINT YOU SYSTEM CHANGES TO .5 LB. PLEASE |
| | SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED |
| | TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | |
| | 5)I THIS A NEW OR EXISTING GAS METER/ SYSTEM? PLEASE |
| | CLARIFY. IF EXISTING THE BTU LOAD OF THE EXISTING GAS |
| | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |