| 2019-08-27 11:37:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | 2. PLEASE SHOW LOCATION OF NEW PANEL. |
| | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE E3602.2 |
| | 4.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC |
| | 225.30 |
| | 6. |
| | 7. |
| | 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER IS THIS |
| | GAS OR ELECTRIC? WPB FBC 107.2.1 |
| | 9. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| | 107.1, 107.2.1, 107.3.5.1.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |
| | [email protected] |
| | |