Plan Review Notes
Plan Review Notes For Permit 19040803
Permit Number 19040803
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-01 10:53:44PLUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PER WPB FBC 107.2.1 AND AS ALLOWED BY WPB FBC
 107.3.4.1 DEFERRED SUBMITTALS, PROVIDE THE COMPLETE
 MANUFACTURER?S INSTALLATION MANUAL AND SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER. HEATER'S EFFICIENCY MUST
 SHOW AS MIN .92EF TO MATCH THE R405 ENERGY FORM. THE KW
 AND AMPERAGE SHALL MATCH THE ELECTRICAL LOAD TABLE ON
 PLAN PAGE 7 OF 7. THE HEATER MUST BE ABLE TO PRODUCE
 HOT WATER 110F TO MULTIPLE FIXTURES AT THE SAME TIME.
 THIS SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN
 PLACE PRIOR TO FINAL INSPECTION. CONTRACTOR PROCEEDS AT
 HIS OWN RISK.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL. IT IS NOTED THAT A CODE COMPLIANT SANITARY
 RISER DIAGRAM HAS BEEN SUBMITTED. STRUCTURAL DESIGN AND
 FIXTURE LOCATIONS MAY WELL REQUIRE ADDITIONAL VENTRS
 AND PIPING CONFIGURATIONS. IT IS THE CONTRACTOR'S
 RESPONSIBILITY TO PROVIDE A CODE COMPLIANT
 INSTALLATION.
 3. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 WASHING MACHINE, ICE LINE AND DISHWASHER. FBC RES
 P2903.5
 4. THE COMBINED DISCHARGE FROM A DISHWASHER AND A ONE-
 OR TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE
 DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN
 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER
 DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF
 THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT
 POSITION BEFORE CONNECTING TO THE HEAD OF THE FOOD
 WASTE DISPOSAL OR TO A TEE-WYE FITTING IN THE SINK
 TAILPIECE. FBC RES P2717.2
 5. SHUT OFF VALVES FOR THE UNDER COUNTER WASHING
 MACHINE AND ICE MAKER SHALL BE ACCESSIBLE. FBC RES
 P2903.9.4