Date Text
2019-05-02 15:49:53PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE THE COMPLETE INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER. HEATER'S EFFICIENCY MUST SHOW AS
 MIN .92EF TO MATCH THE R405 ENERGY FORM. PROVIDE HEAT
 RISE CHART AS ON SHT #7 THE KW RATING IS LISTED AS
 4.5KW. THE HEATER MUST BE ABLE TO PRODUCE HOT WATER
 110F TO MUILT FIXTURES AT THE SAME TIME. FBC 107.2.1
  
 2) MIN TRAP SIZE FOR A WASHING MACHINE IS 2". PLAN ON
 SHT.#7 CALLS OUT 1 1/2". FBC P 709.1
  
 3) DISHWASHER SHALL DISCHARGE BY MEANS OF AIR GAP AND
 NOT DIRECTLY CONNECT INTO THE STACK. FBC-P 802.1.6
  
 4) TANKLESS SHALL HAVE CLEAR ACCES TO ALLOW FOR
 OBSERVATIONS, MAINTENANCE, SERVICING, AND REPLACING.
 FBC-R P 2801.5
  
 5) PROVIDE SHOWER PAN DETAIL. SHOW PRE-PITCH, FINISHED
 CURB HEIGHT AND SHOWER PAN MATERIAL BEING USED FBC
 107.2.1
  
 6) PROVIDE LOCATION ON PLAN WHERE THE SHUT OFF VALVES
 FOR THE UNDER COUNTER WASHING MACHINE AND ICE MAKER ARE
 LOCATED. VALVES SHALL HAVE READY ACCESSIBLE. FBC-R
 P2903.9.4
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  