| 2019-05-20 14:52:30 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1ST BUILDING PLAN REVIEW DENIED: |
| | |
| | 1. FBC B 107.2.1 THE DETAILS FOR LINTEL #21 ON SHEETS |
| | 4/7 & 5/7 ARE NOT CLEAR AS TO MEETING THE REQUIRED LOAD |
| | CAPACITY. PLEASE ADJUST AND CLARIFY. |
| | |
| | 2. FBC B 109.3 THE VALUATION OF THIS APPLICATION |
| | APPEARS TO BE VERY LOW. PLEASE ADJUST AND CLARIFY. |
| | |
| | 3. FBC B 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR, AND |
| | OVERHEAD GARAGE DOOR SUBMITTALS. |
| | |
| | NOTES: |
| | A. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. |
| | CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT |
| | ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF. |
| | |
| | B. A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK. |
| | |
| | C. BALCONY AND STAIR HANDRAIL SUBMITTALS ARE REQUIRED |
| | TO BE APPROVED BY THE DESIGNER OF RECORD. |
| | |
| | D. A BLOWER DOOR TEST, FOR AIR LEAKAGE, HAS TO BE |
| | COMPLETED BY THIRD PARTY AND IS REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF C.O. AS PER FBC EC |
| | R402.4.1.2. |
| | |