Plan Review Notes
Plan Review Notes For Permit 19040803
Permit Number 19040803
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-20 14:52:30***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1ST BUILDING PLAN REVIEW DENIED:
  
 1. FBC B 107.2.1 THE DETAILS FOR LINTEL #21 ON SHEETS
 4/7 & 5/7 ARE NOT CLEAR AS TO MEETING THE REQUIRED LOAD
 CAPACITY. PLEASE ADJUST AND CLARIFY.
  
 2. FBC B 109.3 THE VALUATION OF THIS APPLICATION
 APPEARS TO BE VERY LOW. PLEASE ADJUST AND CLARIFY.
  
 3. FBC B 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR, AND
 OVERHEAD GARAGE DOOR SUBMITTALS.
  
 NOTES:
 A. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF.
  
 B. A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK.
  
 C. BALCONY AND STAIR HANDRAIL SUBMITTALS ARE REQUIRED
 TO BE APPROVED BY THE DESIGNER OF RECORD.
  
 D. A BLOWER DOOR TEST, FOR AIR LEAKAGE, HAS TO BE
 COMPLETED BY THIRD PARTY AND IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF C.O. AS PER FBC EC
 R402.4.1.2.
  