| 2019-05-06 13:51:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. OVERCURRENT PROTECTION FOR SERVICE SHOULD BE AT |
| | FIRST MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC |
| | 230.91 |
| | 2. WIRING FROM FPL TO METER AND FROM METER TO FIRST |
| | MEANS OF DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT |
| | GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.6 |
| | 3. GROUNDING ELECTRODE CONDUCTOR SHOULD BE WIRED TO THE |
| | FIRST MEANS OF DISCONNECT OR THE METER CAN, BUT NOT |
| | TIED INTO THE SUB-PANEL. THE GROUNDING ELECTRODE |
| | CONDUCTOR IS CONNECTED IN ONE LOCATION ONLY. PROVIDE |
| | CORRECTION. NEC 250.24 |
| | 4. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| | GROUNDING ELECTRODE. THIS GROUNDING ELECTRODE NEEDS TO |
| | BE AUGMENTED BY AN ADDITIONAL ELECTRODE AT LEAST 6 FEET |
| | AWAY OR PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 |
| | OHMS OR LESS. PROVIDE CORRECTION. NEC 250.53(A)(2) |
| | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 6. PROVIDE SERVICE AREA RECEPTACE WITH GFCI PROTECTION. |
| | NEC 210.64, 210.8 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |