Plan Review Notes
Plan Review Notes For Permit 19040782
Permit Number 19040782
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-18 16:51:09PLUMBING 1ST REVIEW**DENIED** PLANS HAVE BEEN REVIEW
 USING CURRENT 2017 6TH ED. FLORIDA BUILDING CODE. A GAS
 PLAN AND PERMIT APPLICATION IS REQUIRED.
  
  
 1) SHT P-2 IS CALL OUT FOR GAS TITAN N-120 11.8KW.
 THERE IS NO SUCH HEATER. PLEASE CLARIFY AND SUPPLY
 MANUFACUTURE INSTALLATION MANUAL. IF THIS IS GOING TO
 BE GAS PLEASE CALL THIS REVIEWER AND I WILL EMAIL YOU
 THE REQUIREMENT CHECK LIST FOR GAS. FBC 107.3.5
  
 2) PROVIDE A CORRECTED R405 FORM AS THE CURRENT ONE IS
 LISTED A 50 GALLON ELECTRIC TANK WATER HEATER AT E.F
 90. THE CURRENT MIN FEDERAL REQUIREMENT IS E.F .95 OR
 U.E.F .92 ALSO YOU HAVE TANKLESS HEATERS ON MUILT
 SHEETS. FBC 107.2.1
  
 3) IT APPEARS THE WASHING MACHINE IS DISCHARGING INTO
 THE BATHROOM GROUP WET VENT. PLEASE CORRECT AND SHOW
 CONECTION DOWNSTREAM OF BATHROOM GROUPS. FBC P 912.1
  
 4) PROVIDE A CLEAR DETAIL OF PLUMBING FLAT DRAWING
 SIMILAR TO THE E-SHEETS AND LIST FIXTURE TYPE ON
 PLUMBING ISOMETRIC. FBC 107.3.5
  
 5) SHOW RPZ BACKFLOW ON MAIN WATER SERVICE AND LIST ON
 PLAN SEPERATE PERMIT REQUIRED BY LICENSE PLUMBING ONLY.
 PER WPB CROSS CONNECTION MANUAL
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH