| Plan Review Notes For Permit 19040782 |
| Permit Number |
19040782 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-18 16:51:09 | PLUMBING 1ST REVIEW**DENIED** PLANS HAVE BEEN REVIEW | | | USING CURRENT 2017 6TH ED. FLORIDA BUILDING CODE. A GAS | | | PLAN AND PERMIT APPLICATION IS REQUIRED. | | | | | | | | | 1) SHT P-2 IS CALL OUT FOR GAS TITAN N-120 11.8KW. | | | THERE IS NO SUCH HEATER. PLEASE CLARIFY AND SUPPLY | | | MANUFACUTURE INSTALLATION MANUAL. IF THIS IS GOING TO | | | BE GAS PLEASE CALL THIS REVIEWER AND I WILL EMAIL YOU | | | THE REQUIREMENT CHECK LIST FOR GAS. FBC 107.3.5 | | | | | | 2) PROVIDE A CORRECTED R405 FORM AS THE CURRENT ONE IS | | | LISTED A 50 GALLON ELECTRIC TANK WATER HEATER AT E.F | | | 90. THE CURRENT MIN FEDERAL REQUIREMENT IS E.F .95 OR | | | U.E.F .92 ALSO YOU HAVE TANKLESS HEATERS ON MUILT | | | SHEETS. FBC 107.2.1 | | | | | | 3) IT APPEARS THE WASHING MACHINE IS DISCHARGING INTO | | | THE BATHROOM GROUP WET VENT. PLEASE CORRECT AND SHOW | | | CONECTION DOWNSTREAM OF BATHROOM GROUPS. FBC P 912.1 | | | | | | 4) PROVIDE A CLEAR DETAIL OF PLUMBING FLAT DRAWING | | | SIMILAR TO THE E-SHEETS AND LIST FIXTURE TYPE ON | | | PLUMBING ISOMETRIC. FBC 107.3.5 | | | | | | 5) SHOW RPZ BACKFLOW ON MAIN WATER SERVICE AND LIST ON | | | PLAN SEPERATE PERMIT REQUIRED BY LICENSE PLUMBING ONLY. | | | PER WPB CROSS CONNECTION MANUAL | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|