| 2019-04-19 17:16:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION. PLEASE SEE NEC |
| | 220.85. METHOD USED FOR LOAD CALC WAS FOR 3 OR MORE |
| | DWELLINGS. 220.84 CAN BE USED IF THE LOAD CALC FOR 3 |
| | IDENTICAL UNITS UNDER 220.84 IS LESS THAN THE NORMAL |
| | CALCULATION IN PART III FOR 2 UNITS. FBC 107.2.1 NEC |
| | 220 |
| | |
| | 2. SPECIFY "OTHER LOADS" IN LOAD CALC. NEC 220 FBC |
| | 107.2.1 |
| | |
| | 3. NO HOUSE PANEL BUT HOUSE PANEL SHOWN IN LOAD CALC, |
| | PROVIDE CORRECTION. FBC 107.2.1 |
| | |
| | 4. OVER HANG OF COUNTERTOP IN APARTMENT B IS MORE THAN |
| | 6''. RECEPTACLE LOCATION IN PENINSULAR IS NOT CODE |
| | COMPLIANT. PROVIDE CORRECTION. NEC 210.52C5 (EXCEPTION |
| | TO #5) |
| | |
| | 5. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF INSTAHOT. |
| | FBC 107.2.1 NEC 90.7, 110.2, 110.3B |
| | |
| | 6. PROVIDE ATLEAST ONE RECEPTACLE ON PENINSULAR ISLAND |
| | THAT IS CODE COMPLIANT AND NOT UNDER THE OVERHAND OF |
| | THE COUNTERTOP IN APARTMENT C. NEC 210.52C5 (EXCEPTION |
| | TO #5) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |