Plan Review Notes
Plan Review Notes For Permit 19040782
Permit Number 19040782
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-17 14:09:48BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. SEE PLAN PAGE A4.02. STAIR DETAIL REFERENCES DETAILS
 D,E&F 4.03. PLAN PAGE 4.03 IS MISSING. REVIEW OF STAIRS
 IS NOT COMPLETE.
  
 2. SEE STAIR DETAIL ON PAGE A4.02, OPENING BETWEEN
 GUARD AND STAIR SHALL NOT EXCEED 4 INCHES PER R312.1.3.
  
 3. STATE GOVERNING CODES ON COVER PAGE.
  
 4. ROOFING PERMIT REQUIRED.
  
 5. PROVIDE DESIGN PRESSURES OF ALL WINDOW AND EXTERIOR
 DOOR OPENINGS. PLACE ON WINDOW AND DOOR SCHEDULE OR
 PLACE ON PLAN NEXT TO EACH OPENING.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 6. REF. PLAN PAGE A4.00. EXTERIOR WALL INSULATION IS
 SHOWN AS R-19 FOR 2ND FLOOR WOOD FRAMED WALLS. THE
 ENERGY SUBMITTAL DOES NOT HAVE ENERGY DATA FOR WOOD
 FRAMED WALLS. PLEASE CLARIFY
  
 7. REF. PLAN PAGE A4.00. R VALUE MISSING FROM PLAN FOR
 CMU EXT. WALL INSULATION. ENERGY SUBMITTAL SHOWS R4.1.
 PLEASE CLARIFY.
  
 8. THERE IS A CONFLICT BETWEEN PLAN PAGE D1.01 -
 PARTITIONS AND BEARING WALLS TO REMAIN AND PLAN PAGE
 A1.02 (B) NEW EXTERIOR WALLS. PLEASE CLARIFY.
  
 9. THERE IS A CONFLICT BETWEEN PLAN PAGE D1.02 -
 PARTITIONS AND BEARING WALLS TO REMAIN AND PLAN PAGE
 A1.03 (A) NEW EXTERIOR WALLS. PLEASE CLARIFY.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
2019-04-25 15:04:11PLAN REVIEWER, PLEASE EVALUATE THE APPROPRIATENESS OF
 REVOKING 17061319. ALSO LOOK AT ALL RECORDS TO
 DETERMINE ESTABLISHED UNITS ON PROPERTY AND APPLICABLE
 CODES, EXISTING & FBC OR RESIDENTIAL?. SAK