| Plan Review Notes For Permit 19040741 |
| Permit Number |
19040741 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-07-12 06:44:43 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. I HAVE INCLUDED A COPY OF THE MOST RECENT | | | GAS DRAWING ON FILE IN THE APPLICATION PACKAGE TO BE | | | USED AS REFERENCE ONLY. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | | G2413.2, G2413.3. WPB AMEND. TO FBC SEC. 107.1.3RD | | | REQUEST. | | | 2) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING | | | INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER. | | | WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST. | | | PLEASE CALL THIS REVIEWER TO REVIEW THESE COMMENTS | | | PRIOR TO RESUBMITTAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|