| Plan Review Notes For Permit 19040733 |
| Permit Number |
19040733 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-16 16:30:36 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PROVIDE A LEGIBLE SET OF PLANS SHOWING PIPING AND | | | PIPE SIZES, LOCATION OF RAIN SENSOR, CONNECTION POINT | | | TO THE HOMES WATER SYSTEM AND STAND ALONE BACKFLOW | | | PREVENTER FOR THE IRRAGATION SYSTEM. FBC 107.3.5 A | | | SEPERATE BACKFLOW PERMIT IS REQUIRED THE IRRAGATION | | | SYSTEM IS ONLY PERMITTED TO BE INSTALLED BY A LICENSE | | | PLUMBING CONTRACTOR. | | | | | | 2) THE RPZ BACKFLOW THAT YOU CLAIM IS EXISTING IS NOT | | | SHOWING UP UNDER PERMIT RECORDS. WHEN WAS THIS DEVICE | | | INSTALLED? FBC 107.2.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|