| Plan Review Notes For Permit 19040725 |
| Permit Number |
19040725 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-25 14:29:32 | PLUMBING 1ST REVIEW**DENIED** | | | | | | | | | 1) YOU DESIGN LAY OUT SEEM TO NO LONGER HAVE AN | | | ACCESSIBLE ROUTE TO THE TOILETROOM FOR THE PUBLIC. | | | REDUCTION IN ACCESS IS PROHIBITED UNDER FBC-ACC | | | 202.3.1. PROVIDE AN ACCESSIBLE ROUTED AND SAFE ACCESS | | | FOR THE PUBLIC TO USE THE TOILET ROOM AND DRINKING | | | FOUNTAIN AS DESIGNED AND APPROVED ON PERMIT#13090901 | | | SHT A002. | | | | | | 2) SHT A003 SHOWS GRAB BARS LOCATED AT 36" TO THE | | | CENTER. ALL GRAB BARS SHALL BE 33"-36" TO THE TOP | | | GRIPPING SURFACE. FBC-ACC 609.4 | | | | | | 3) SHT A003 SHOWS CABINET 36" TO THE BOTTOM. FBC-ACC | | | 606.3 LIST MAX 34" TO THE TOP OF COUNTER TOP OR RIM OF | | | SINK WHICH EVER IS GREATER. | | | | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | | | | | | | |
|