2019-04-25 14:29:32PLUMBING 1ST REVIEW**DENIED**
  
  
 1) YOU DESIGN LAY OUT SEEM TO NO LONGER HAVE AN
 ACCESSIBLE ROUTE TO THE TOILETROOM FOR THE PUBLIC.
 REDUCTION IN ACCESS IS PROHIBITED UNDER FBC-ACC
 202.3.1. PROVIDE AN ACCESSIBLE ROUTED AND SAFE ACCESS
 FOR THE PUBLIC TO USE THE TOILET ROOM AND DRINKING
 FOUNTAIN AS DESIGNED AND APPROVED ON PERMIT#13090901
 SHT A002.
  
 2) SHT A003 SHOWS GRAB BARS LOCATED AT 36" TO THE
 CENTER. ALL GRAB BARS SHALL BE 33"-36" TO THE TOP
 GRIPPING SURFACE. FBC-ACC 609.4
  
 3) SHT A003 SHOWS CABINET 36" TO THE BOTTOM. FBC-ACC
 606.3 LIST MAX 34" TO THE TOP OF COUNTER TOP OR RIM OF
 SINK WHICH EVER IS GREATER.
  
  
  
  