Plan Review Notes
Plan Review Notes For Permit 19040705
Permit Number 19040705
Review Stop P
Sequence Number 3
Notes
Date Text
2019-08-08 11:58:341) PLEASE PROVIDE A RESPONSE NARRATIVE THAT CLEARLY
 DESCRIBES THE CHANGES BEING MADE TO THE PLUMBING SYSTEM
 AND THAT RESPONDS TO THE PREVIOUS PLAN REVIEW COMMENTS
 DATED 6/20/19 AND ALSO TO THESE COMMENTS.. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) INSERT THE REVISED PLUMBING PLANS INTO THE MASTER
 SET OF PLANS.WPB AMEND. TO FBC SEC. 107.1.
 3) IT IS OBVIOUS THE DEVELOPED LENGTH DISTANCE FROM THE
 SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRES HOT
 WATER EXCEEDS 50 FEET. THEREFORE A HOT WATER
 RECIRCULATING SYSTEM WILL BE REQUIRED PER 2017
 FBC-PLUMBING SEC.607.2. 3RD REQUEST.
 4) THE HOT WATER SYSTEM SHALL BE INSULATED IN
 ACCORDANCE WITH 2017 FBC-PLUMBING SEC.607.5 AND THE
 2017 FBC-ENERGY SEC. C404.4 AND TABLE C403.2.10.
 5) A RECIRCULATING PUMP IS REQUIRED ON THE
 RECIRCULATION SYSTEM AND MUST BE INSTALLED IN
 ACCORDANCE WITH 2017 FBC-ENERGY SEC.C404.6.1.
 6) A MOP SINK IS REQUIRED FOR THIS OCCUPANCY PER 2017
 FBC-PLUMBING TABLE. 403.1. 3RD REQUEST.
 7) SUBMIT A COMPLETE KITCHEN EQUIPMENT SCHEDULE. THERE
 ARE SYMBOLS USED FOR KITCHEN EQUIPMET ON SHT. P1.1.
 THAT ARE NOT ON THE SCHEDULE ON SHT. P0.1. CLARIFY.
 8) SHT.P1.2 HAS A NOTE THAT STATES THE MOP SINK WILL BE
 INSTALLED UNDER A SEPARATE PERMIT. WHY IS THIS BEING
 DONE? THE MOP SINK SHALL BE INSTALLED UNDER THIS PERMIT
 NUMBER AND SHALL CONNECT TO THE GREASE INTERCEPTOR.
 2017 FBC-PLUMBING SEC.1003..3.1.
 9) THIS SUBMITTAL IS CONFUSING. THE REVISED PLUMBING
 PLANS HAVE AN ADDRESS ON THEM AS 518 S. DIXIE HWY.AND
 THE OTHER PLANS NOTE THE ADDRESS AS 327 HIBISCUS.
 CLARIFY. IN ADDITION, REVISED SHEET S-102R SHOWS
 INDIVIDUAL TENANT SPACES BUT THESE SPACES ARE NOT SHOWN
 ON ANY OTHER PLAN. CLARIFY.
 10) SHT.P1.2 - SHOWS TWO TANKLESS WAATER HEATERS BUT
 THE DETAIL ON SHT. P0.1 ONLY SHOWS ONE. IF THESE ARE
 PIPED IN SERIES, BOTH WATER HEATERS SHALL BE SHOWN ON
 THE DETAIL. WPB AMEND. TO FBC-SEC.107.2.1.
 11) 3RD REQUEST.HALLWAY FLOOR DRAINS ARE NOT INSTALLED
 AS THIS REVISION SHOWS AND ARE ALREADY INSTALLED.
 PLEASE CLARIFY. FBC 107.2.1
 12) SHT. P1.1 - THE HAND SINK (B7) AND FIXTURE B2
 DUMPING INTO FLOOR SINKS IN THE COFFEE BAR AREA SHALL
 DISCHARGE TO THE GREASE WASTE SYSTEM. FBC 1003.3.1.
 13) SHT.P1.1 - IDENTIFY EQUIPMENT # D1A, D4, D5, D6, D7
 D16A, #K32 THESE FIXTURES MAY HAVE TO DISCHARGE THROUGH
 THE GREASE WASTE SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  