Plan Review Notes
Plan Review Notes For Permit 19040705
Permit Number 19040705
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-20 14:01:52PLUMBING 2ND REVIEW**DENIED**
  
 1) ANSWERED**PROVIDE A NARRATIVE AS TO WHAT IS CHANGING
 ON THIS REVISION. FBC 107.2.1
  
 2) 2ND REQUEST RETURN LINE REQUIRED IF TOTAL PIPE
 LENGHT IS OVER 50' PLUMBING WATER ISOMETRIC IS MISSING
 THE HOT WATER RETURN PIPING CALL OUT IN SHT. P.01 WATER
 HEATER DETAIL AND REQUIRED WHEN THE OVERALL DEVELOPED
 LENGHT FROM THE WATER HEATER IS OVER 50'. TO ANY
 FIXTURE FBC 107.3.5, FBC-P 607.2
  
 3) 2ND REQUEST. THERE IS NO MOP SINK ON THE PERMIT
 NUMBERS YOUPROVIDED. YOU MUST INCLUDE THE MOP SINK ON
 THIS PLAN AND SHOW IT DISCHARGE INTO THE GREASE
 INTERCEPTOR. NOTE THIS WILL MAY CHAGE THE SIZING
 REQUIREMENTS OF THE GREASE INTERCEPTOR .YOU HAVE NOTES
 ON 2 DIFFERENT PAGES REGARDING THE MOP SINK. CURRENTLY
 NO MOP SINK EXIST AND NO OTHER SEPARATE PERMIT CAN BE
 LOCATED. THE MOP SINK IS A REQUIREMENT PER FBC-P 403.1.
 INCLUDE MOP SINK ON YOUR PLANS OR PROVIDE PERMIT NUMBER
 THAT MOP SINK IS LOCATED ON. FBC 107.3.5
  
 4) 2ND REQUEST.HALLWAY FLOOR DRAINS ARE NOT INSTALLED
 AS THIS REVISION SHOWS AND ARE ALREADY INSTALLED.
 PLEASE CLARIFY. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  