| Plan Review Notes For Permit 19040705 |
| Permit Number |
19040705 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-20 14:01:52 | PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) ANSWERED**PROVIDE A NARRATIVE AS TO WHAT IS CHANGING | | | ON THIS REVISION. FBC 107.2.1 | | | | | | 2) 2ND REQUEST RETURN LINE REQUIRED IF TOTAL PIPE | | | LENGHT IS OVER 50' PLUMBING WATER ISOMETRIC IS MISSING | | | THE HOT WATER RETURN PIPING CALL OUT IN SHT. P.01 WATER | | | HEATER DETAIL AND REQUIRED WHEN THE OVERALL DEVELOPED | | | LENGHT FROM THE WATER HEATER IS OVER 50'. TO ANY | | | FIXTURE FBC 107.3.5, FBC-P 607.2 | | | | | | 3) 2ND REQUEST. THERE IS NO MOP SINK ON THE PERMIT | | | NUMBERS YOUPROVIDED. YOU MUST INCLUDE THE MOP SINK ON | | | THIS PLAN AND SHOW IT DISCHARGE INTO THE GREASE | | | INTERCEPTOR. NOTE THIS WILL MAY CHAGE THE SIZING | | | REQUIREMENTS OF THE GREASE INTERCEPTOR .YOU HAVE NOTES | | | ON 2 DIFFERENT PAGES REGARDING THE MOP SINK. CURRENTLY | | | NO MOP SINK EXIST AND NO OTHER SEPARATE PERMIT CAN BE | | | LOCATED. THE MOP SINK IS A REQUIREMENT PER FBC-P 403.1. | | | INCLUDE MOP SINK ON YOUR PLANS OR PROVIDE PERMIT NUMBER | | | THAT MOP SINK IS LOCATED ON. FBC 107.3.5 | | | | | | 4) 2ND REQUEST.HALLWAY FLOOR DRAINS ARE NOT INSTALLED | | | AS THIS REVISION SHOWS AND ARE ALREADY INSTALLED. | | | PLEASE CLARIFY. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|