Plan Review Notes
Plan Review Notes For Permit 19040705
Permit Number 19040705
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-24 07:49:41PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE A NARRATIVE AS TO WHAT IS CHANGING ON THIS
 REVISION. FBC 107.2.1
  
 2) PLUMBING WATER ISOMETRIC IS MISSING THE HOT WATER
 RETURN PIPING CALL OUT IN SHT. P.01 WATER HEATER DETAIL
 AND REQUIRED WHEN THE OVERALL DEVELOPED LENGHT FROM THE
 WATER HEATER IS OVER 50'. TO ANY FIXTURE FBC 107.3.5,
 FBC-P 607.2
  
 3) YOU HAVE NOTES ON 2 DIFFERENT PAGES REGARDING THE
 MOP SINK. CURRENTLY NO MOP SINK EXIST AND NO OTHER
 SEPARATE PERMIT CAN BE LOCATED. THE MOP SINK IS A
 REQUIREMENT PER FBC-P 403.1. INCLUDE MOP SINK ON YOUR
 PLANS OR PROVIDE PERMIT NUMBER THAT MOP SINK IS LOCATED
 ON. FBC 107.3.5
  
 4) HALLWAY FLOOR DRAINS ARE NOT INSTALLED AS THIS
 REVISION SHOWS. PLEASE CLARIFY. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  