| Plan Review Notes For Permit 19040705 |
| Permit Number |
19040705 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-24 07:49:41 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PROVIDE A NARRATIVE AS TO WHAT IS CHANGING ON THIS | | | REVISION. FBC 107.2.1 | | | | | | 2) PLUMBING WATER ISOMETRIC IS MISSING THE HOT WATER | | | RETURN PIPING CALL OUT IN SHT. P.01 WATER HEATER DETAIL | | | AND REQUIRED WHEN THE OVERALL DEVELOPED LENGHT FROM THE | | | WATER HEATER IS OVER 50'. TO ANY FIXTURE FBC 107.3.5, | | | FBC-P 607.2 | | | | | | 3) YOU HAVE NOTES ON 2 DIFFERENT PAGES REGARDING THE | | | MOP SINK. CURRENTLY NO MOP SINK EXIST AND NO OTHER | | | SEPARATE PERMIT CAN BE LOCATED. THE MOP SINK IS A | | | REQUIREMENT PER FBC-P 403.1. INCLUDE MOP SINK ON YOUR | | | PLANS OR PROVIDE PERMIT NUMBER THAT MOP SINK IS LOCATED | | | ON. FBC 107.3.5 | | | | | | 4) HALLWAY FLOOR DRAINS ARE NOT INSTALLED AS THIS | | | REVISION SHOWS. PLEASE CLARIFY. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|