| Plan Review Notes For Permit 19040705 |
| Permit Number |
19040705 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-22 10:37:45 | 1ST REVIEW FBC-2017 MECHANICAL | | | MASTER PERMIT #18100338 | | | REVISION #19040705 | | | 4/22/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE EXHAUST OUTLET FOR VEF-1 MUST BE MINIMUM 3 FT. | | | AWAY FROM THE PROPERTY LINE- SECTION 501.3.1 (3) FBC M. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW SPLIT SYSTEMS- SECTION C403.2.1 FBC EC. | | | | | | 3) POVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR | | | HANDLERS- SECTION 307.2.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|