| 2019-06-12 09:22:35 | 2NDREVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. YOUR SIZING CALCULATION FOR YOUR GREASE INTERCEPTOR |
| | IS INACCURATE THIS FORMULA IS MEANT TO BE USED FOR |
| | LARGER SIT DOWN RESTAURANTS AND IT IS ONLY LISTING 1 |
| | SEAT AND THE PLAN SHOWS 4, YOU NEED TO USE THE |
| | CALCULATIONS THE USE THE VOLUME OF THE SINKS TO |
| | DETERMINE THE GPM ALSO KNOWN AS THE PDI METHOD. IN |
| | ORDER TO APPROVE THIS INTERCEPTOR YOU SHALL PROVIDE |
| | SIZING CALCULATIONS FROM THE MANUFACTURE THEY CAN BE |
| | EASILY FOUND ON THE MANUFACTURE,S WEB SITE. PER FBC PL |
| | 1003.2 AND WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. YOU PROVIDED MANUFACTURE SPECIFICATIONS BUT YOU DID |
| | NOT LIST THE MODEL THAT YOU WILL BE USING PLEASE MARK |
| | THE MODEL ON THE SPECS AND PROVIDE MANUFACTURE |
| | INSTALLATION GUIDE. WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE NOTE ON THE PLAN A SEPARATE PERMIT IS |
| | REQUIRED FOR THE GREASE INTERCEPTOR. PER WPB UTILITIES |
| | DEPT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |