| 2019-05-01 14:20:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET CVR & A 1 - THERE IS AN INDICATION OF ONE EXIT |
| | REQUIRED AND TWO PROVIDED. SHEET A 1 INDICATES THAT THE |
| | BATHROOM AND OFFICE DOORS OPEN INTO THE EXIT CORRIDOR |
| | ENCROACHING INTO THE REQUIRED EGRESS WIDTH. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET E 1 & A 1 - THERE ARE NO INDICTIONS, EXISTING |
| | OR PROPOSED, OF EXITS SIGNS OVER THE EXIT DOORS. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS. |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN |
| | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS |
| | 11 |
| | THROUGH 43. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | PER NFPA 101, NEW MERCANTILE OCCUPANCIES |
| | |
| | 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE |
| | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| | MEANS OF EGRESS |
| | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE IS AN INCORRECT REFERENCE, 2014, |
| | OF NFPA. IS THIS REFERENCE A GENERAL REFERENCE OR |
| | SPECIFIC ONE? |
| | |
| | THE CURRENT EDITION OF NFPA 1 PER THE FLORIDA FIRE |
| | PREVENTION CODE IS 2015. |
| | |
| | PLEASE REVIEW ANC CLARIFY AND/OR CORRECT. |
| | |
| | |
| | |
| | 4) SHEET CVR - THE IS AN INDICATION UNDER CODE RESEACH: |
| | OCCUPANCY, OF BUSINESS (B GROUP) |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE THIS WOULD BE |
| | CONSIDERED A MERCANTILE OCCUPANCY;(ASSEMBLY LESS THAN |
| | 50) |
| | |
| | PLEASE REVIEW AND PROVIDE A CARRECTIVE NOTE FOR THE |
| | FFPC AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |