| Plan Review Notes For Permit 19040656 |
| Permit Number |
19040656 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2019-10-09 18:51:59 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 4TH BUILDING REVIEW. | | | | | | APPROVED WITH PROVISOS: | | | | | | 7. A REVISION WILL BE REQUIRED FOR FIRE RATING THE | | | RADIO PROPOGATION CONDUITS ENCLOSURE IF DETERMINED TO | | | BE REQUIRED AFTER TESTING HAS BEEN COMPLETED. | | | 9. THE FIRE WATER SUPPLY RISER LOCATED IN THE STAIR | | | LANDING OF GROUND FLOORPLAN (BLDG.B SOUTH) MUST BE | | | REMOVED AND RELOCATED AS PER NOTE ON PAGE 005 SHEET | | | A1.1. | | | 19. ALL PRODUCT APPROVALS FOR: ROOF HATCHES, EIFS | | | SYSTEM, ROOF TOP VENTILATORS, SHUTTERS, AND SKY LIGHTS | | | NEED TO BE REVIEW STAMPED AND SIGNED BY DESIGNER OF | | | RECORD. | | | | | | | | | |
|