| 2019-09-05 13:43:14 | 2ND REVIEW: 19040656 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT PS1 NOTES ON THE OVERFLOW STORM DRAIN STATES |
| | OVERFLOW DRAIN CONNECT TO CATCH BASIN THEY SHALL COMPLY |
| | WITH FBC PL FBC PL 1108.2 SEPARATE SYSTEMS REQUIRED. |
| | SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT |
| | OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM. |
| | DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT |
| | WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| | MAINTENANCE PERSONNEL |
| | |
| | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 2ND REQUEST 3. PROVIDE A PLUMBING FIXTURE BREAKDOWN |
| | BROKEN DOWN BY BUILDING AND OCCUPANT LOAD. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |