Plan Review Notes
Plan Review Notes For Permit 19040656
Permit Number 19040656
Review Stop M
Sequence Number 2
Notes
Date Text
2019-08-16 17:26:432ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040656
 8/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW NOT COMPLETELY ADDRESSED.
 1) COMMENT #1 STILL EXISTS: THE REQUESTED AC COOLING
 AND HEATING CALCULATIONS FOR THE SYSTEMS WERE NOT
 SUBMITTED.
 2) COMMENT #2 STILL EXISTS: THE ENERGYGAUGE COMPLIANCE
 SUBMITTALS DO NOT INCLUDE DATA FOR THE 3.5 AND 4.0-TON
 SYSTEMS. THE SYSTEMS LISTED IN THE REPORTS ARE ALL 5.0
 TON, AND MANY OF THE SYSTEM NUMBERS DO NOT CORRELATE
 WITH SYSTEM NUMBERS SHOWN IN THE EQUIPMENT SCHEDULE ON
 SHEET M9. PLEASE RESUBMIT CORRECTED REPORTS, AND PLEASE
 DESIGNATE WHICH BUILDINGS THE REPORTS ARE FOR.
 3) COMMENT #3 STILL EXISTS: AC AND VENTILATIONS
 CALCULATIONS, AND LAYOUT PLANS NOT PROVIDED FOR THE NEW
 BUILDINGS D & E. THE ENGINEER?S AND ARCHITECT?S
 RESPONSE REFERENCE SHEET M8.1 FOR CORRECTIONS, HOWEVER
 THAT SHEET IS SHOWING C BUILDING, NOT D OR E.
 4) COMMENT #4 STILL EXISTS: PROVIDE DATA FROM THE
 MANUFACTURER TO INDICATE THE 5.0-TON SYSTEMS CANNOT
 PRODUCE OVER 2000 CFMS OF SUPPLY AIR WHEN RUN AT ANY
 SPEED. OTHERWISE PLEASE PROVIDE DS DETECTORS IN THE
 SUPPLY SYSTEMS OF THE 5.0 SYSTEMS.
 5) COMMENT #5 STILL PARTIALLY EXISTS- NEED TO VERIFY
 O/A INLETS ARE LOCATED 10? AWAY FROM ROADS, DRIVEWAYS,
 AND PARKING LOTS.
 6) NO RESPONSES WERE PROVIDED FOR 1ST REVIEW COMMENTS
 #6, 7, & 8. SEE COMMENTS COPIED BELOW AND COMPLY.
  
  6) SHEET M9: SUBMIT THE ROOF STAND NOA #17-1218.06
 WITH
  INSTALLATION DETAILS MARKED UP BY THE ENGINEER OF
  RECORD- RULE 9N-3 FAC, OR PROVIDE COMPLETE ENGINEERED
  DETAILS ON THE PLANS- SECTION 301.15
  
  7) M9: CORRECT THE RESIDENTIAL CODE REFERENCE SHOWN IN
  THE SIDEWALL GRILL DETAIL- SECTION 603.1 FBC M.
  
  8) SUBMIT THE NOA FOR THE HOISTWAY OPENING LOUVERS
 WITH
  APPROVAL STAMP BY THE EOR, AND INDICATE THAT A CLASS
  1MOTORIZED DAMPER WILL BE INSTALLED AT THE OPENING IN
  COMPLIANCE WITH SECTION C403.2.4.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401