| Plan Review Notes For Permit 19040656 |
| Permit Number |
19040656 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-06 16:15:16 | 2ND REVIEW COMMENTS: | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) COMPLIED | | | | | | | | | | | | 2) DID NOT COMPLY, FIRE SPRINKLER BY OTHERS DOES NOT | | | MEET THIS REQUIREMENT; | | | | | | PREVIOUS COMMENT RESUBMITTED: | | | | | | SHEET 0.1 COV & A1.0 - FOR CLARIFICATION PURPOSES, EVEN | | | IF THERE IS EXISITNG FIRE SPRINKLER PROTECTION WITHIN | | | ANY OF THE BUILDINGS THE EXTENT OF THE SPRINKLER DESIGN | | | REQUIRES F.A.C. 61G DOCUMENTS WITH THIS MASTER PERMIT. | | | | | | PLEASE PROVIDE THE REQUIRED DOCUMENTS IN ETHER PLAN | | | DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY THE | | | EOR.(SHOP DRAWINGS SHALL BE SUBMITED BASED ON THESE) | | | (SHOULD THE EOR DEFER, A LETTER NEEDS TO BE SUBMITTED; | | | HOWEVER, THE DEFERRED EOR WILL NEED TO SUBMIT 61 G | | | DOCUMENTS WITH THE MASTER) | | | | | | PLEASE REVIEW AND PROVIDE WITH THIS MASTER | | | | | | | | | | | | 3) COMPLIED. | | | | | | | | | | | | 4) COMPLIED | | | | | | | | | | | | 5) COMPLIED | | | | | | | | | 6) COMPLIED | | | | | | | | | | | | 7) COMPLIED | | | | | | 7A) COMPLIED | | | | | | 7B) COMPLIED | | | | | | 7C) COMPLIED | | | | | | 7D) COMPLIED | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|