2019-08-06 16:15:162ND REVIEW COMMENTS:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COMPLIED
  
  
  
 2) DID NOT COMPLY, FIRE SPRINKLER BY OTHERS DOES NOT
 MEET THIS REQUIREMENT;
  
 PREVIOUS COMMENT RESUBMITTED:
  
 SHEET 0.1 COV & A1.0 - FOR CLARIFICATION PURPOSES, EVEN
 IF THERE IS EXISITNG FIRE SPRINKLER PROTECTION WITHIN
 ANY OF THE BUILDINGS THE EXTENT OF THE SPRINKLER DESIGN
 REQUIRES F.A.C. 61G DOCUMENTS WITH THIS MASTER PERMIT.
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTS IN ETHER PLAN
 DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY THE
 EOR.(SHOP DRAWINGS SHALL BE SUBMITED BASED ON THESE)
 (SHOULD THE EOR DEFER, A LETTER NEEDS TO BE SUBMITTED;
 HOWEVER, THE DEFERRED EOR WILL NEED TO SUBMIT 61 G
 DOCUMENTS WITH THE MASTER)
  
 PLEASE REVIEW AND PROVIDE WITH THIS MASTER
  
  
  
 3) COMPLIED.
  
  
  
 4) COMPLIED
  
  
  
 5) COMPLIED
  
  
 6) COMPLIED
  
  
  
 7) COMPLIED
  
 7A) COMPLIED
  
 7B) COMPLIED
  
 7C) COMPLIED
  
 7D) COMPLIED
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]