| 2019-06-10 17:58:29 | 1ST REVIEW: 19040656 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE STORM WATER ISOMETRIC DRAWING AND SHOW |
| | TERMINATION POINT OF THE OVERFLOW DRAINS PER WPB AMEND |
| | TO FBC 107.3.5.1.3(13) AND FBC PL 1108.2 SEPARATE |
| | SYSTEMS REQUIRED. |
| | SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT |
| | OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM. |
| | DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT |
| | WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| | MAINTENANCE PERSONNEL. |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER |
| | HEATER AND THE ELEVATOR SUMP PUMP. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. PROVIDE A PLUMBING FIXTURE BREAKDOWN BROKEN DOWN BY |
| | BUILDING AND OCCUPANT LOAD. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |