2019-06-11 17:13:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040656
 6/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) PROVIDE ENERGY CALCULATIONS FOR THE NEW BUILDINGS,
 AND THE PREVIOUSLY UNCONDITIONED WAREHOUSE BUILDINGS
 THAT ARE NOW BEING CONDITIONED. REFER TO SECTIONS
 C101.2, C101.5.1, C103.1, C103.1.1, C401.2 AND C503.2
 FBC EC.
  
 3) PLEASE NOTE THAT ALONG WITH THE MISSING CALCS LISTED
 ABOVE, ALSO MISSING ARE AC LAYOUT PLANS AND VENTILATION
 CALCULATIONS FOR THE NEW BUILDINGS D ND E- SECTION
 107.2.1 WPB.
  
 4) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR
 SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS ARE
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
 PLEASE PROVIDE SYMBOLS ON THE PLANS TO SHOW THE
 LOCATIONS OF THE DEVICES, AND INDICATE HOW THEY WILL BE
 SUPERVISED IN ACCORDANCE WITH SECTION 606.4.1 FBC M.
  
 5) VERIFY THE O/A INLETS HAVE A MINIMUM 10' CLEARANCE
 TO EXHAUST OUTLETS, VENTS, DRIVEWAYS, ROADS, AND
 PARKING LOTS- SECTION 401.4 FBC M. INDUICATE HOW THE
 OPENIINGS WILL BE PROTECTED PER SECTION 401.5 FBC M.
  
 6) SHEET M9: SUBMIT THE ROOF STAND NOA #17-1218.06 WITH
 INSTALLATION DETAILS MARKED UP BY THE ENGINEER OF
 RECORD- RULE 9N-3 FAC, OR PROVIDE COMPLETE ENGINEERED
 DETAILS ON THE PLANS- SECTION 301.15
  
 7) M9: CORRECT THE RESIDENTIAL CODE REFERENCE SHOWN IN
 THE SIDEWALL GRILL DETAIL- SECTION 603.1 FBC M.
  
 8) SUBMIT THE NOA FOR THE HOISTWAY OPENING LOUVERS WITH
 APPROVAL STAMP BY THE EOR, AND INDICATE THAT A CLASS
 1MOTORIZED DAMPER WILL BE INSTALLED AT THE OPENING IN
 COMPLIANCE WITH SECTION C403.2.4.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  