| 2019-06-11 17:13:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040656 |
| | 6/11/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS FOR THE NEW BUILDINGS, |
| | AND THE PREVIOUSLY UNCONDITIONED WAREHOUSE BUILDINGS |
| | THAT ARE NOW BEING CONDITIONED. REFER TO SECTIONS |
| | C101.2, C101.5.1, C103.1, C103.1.1, C401.2 AND C503.2 |
| | FBC EC. |
| | |
| | 3) PLEASE NOTE THAT ALONG WITH THE MISSING CALCS LISTED |
| | ABOVE, ALSO MISSING ARE AC LAYOUT PLANS AND VENTILATION |
| | CALCULATIONS FOR THE NEW BUILDINGS D ND E- SECTION |
| | 107.2.1 WPB. |
| | |
| | 4) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR |
| | SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1. |
| | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS ARE |
| | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | PLEASE PROVIDE SYMBOLS ON THE PLANS TO SHOW THE |
| | LOCATIONS OF THE DEVICES, AND INDICATE HOW THEY WILL BE |
| | SUPERVISED IN ACCORDANCE WITH SECTION 606.4.1 FBC M. |
| | |
| | 5) VERIFY THE O/A INLETS HAVE A MINIMUM 10' CLEARANCE |
| | TO EXHAUST OUTLETS, VENTS, DRIVEWAYS, ROADS, AND |
| | PARKING LOTS- SECTION 401.4 FBC M. INDUICATE HOW THE |
| | OPENIINGS WILL BE PROTECTED PER SECTION 401.5 FBC M. |
| | |
| | 6) SHEET M9: SUBMIT THE ROOF STAND NOA #17-1218.06 WITH |
| | INSTALLATION DETAILS MARKED UP BY THE ENGINEER OF |
| | RECORD- RULE 9N-3 FAC, OR PROVIDE COMPLETE ENGINEERED |
| | DETAILS ON THE PLANS- SECTION 301.15 |
| | |
| | 7) M9: CORRECT THE RESIDENTIAL CODE REFERENCE SHOWN IN |
| | THE SIDEWALL GRILL DETAIL- SECTION 603.1 FBC M. |
| | |
| | 8) SUBMIT THE NOA FOR THE HOISTWAY OPENING LOUVERS WITH |
| | APPROVAL STAMP BY THE EOR, AND INDICATE THAT A CLASS |
| | 1MOTORIZED DAMPER WILL BE INSTALLED AT THE OPENING IN |
| | COMPLIANCE WITH SECTION C403.2.4.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |