Plan Review Notes
Plan Review Notes For Permit 19040656
Permit Number 19040656
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-15 09:50:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A .01 - UNDER MEANS OF EGRESS;A, C & D, THERE
 ARE CODE REFERENCES OF NFPA 101, CH 38. NEW BUSINESS
 OCCUPANCIES.
  
 THIS OCCUPANCY IS STORAGE/S1.
  
 PLEASE REVIEW AND CORRECT THE CODE REFERNCES.
  
  
  
 2) SHEET 0.1 COV & A1.0 - FOR CLARIFICATION PURPOSES,
 EVEN IF THERE IS EXISITNG FIRE SPRINKLER PROTECTION
 WITHIN ANY OF THE BUILDINGS THE EXTENT OF THE SPRINKLER
 DESIGN REQUIRES F.A.C. 61G DOCUMENTS WITH THIS MASTER
 PERMIT.
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTS IN ETHER PLAN
 DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY THE
 EOR.(SHOP DRAWINGS SHALL BE SUBMITED BASED ON THESE)
 (SHOULD THE EOR DEFER, A LETTER NEEDS TO BE SUBMITTED;
 HOWEVER, THE DEFERRED EOR WILL NEED TO SUBMIT 61 G
 DOCUMENTS WITH THE MASTER)
  
 PLEASE REVIEW AND PROVIDE WITH THIS MASTER
  
  
  
 3) SHEET A 1.1 - THERE ARE INDICATIONS OF THE
 RELOCATION OF THE FIRE RISER WHICH MAY INCLUDE
 UNDERGROUND FIRE LINE WORK.
  
 ALL UNDERGROUND FIRE LINE WORK SHALL BE DONE IN
 COMPLIANCE WITH NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A APPLICABLE NOTE.
  
  
  
 4) SHEET A 1.1 - THERE ARE INDICATIONS OF THE
 RELOCATION OF THE FIRE RISER AND TO REFER TO THE CIVIL
 DRAWINGS.
  
 THERE ARE NO CIVIL DRAWINGS ATTACHED OR REFERENCED ON
 THE COVER SHEET.
  
 PLEASE REVIEW AND PROVIDE
  
  
  
 5) SHEET A 1.1 - THERE ARE NO INDICATIONS OF THE
 LOCATION OF EXISITNG OR PROPOSED FIRE HYDRANT LOCATIONS
 OR AND CIVIL DRAWINGS TO REFER TO.
  
 PLEASE REVIEW AND PROVIDE.
  
  
 6) SHEET E 9 - THERE DOES NOT APPEAR TO BE ANY EXIT
 LIGHTS OR EMERGENCY LIGHTS WITHIN THE CORRIDOR OF BLDG
 D.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 7) SHEET DE 1.1 - THERE ARE ROLL-UP DOORS INDICATED
 WITH THE NUMBER 21 THAT APPEAR TO BE AT THE ONLY
 ENTRANCE/EXIT TO THE INTERNAL CORRIDORS.
  
 7A) AS THESE DOORS ARE EXITS, HOW WILL THEY BE SECURED
 IN PLACE?
  
 7B) HOW WILL THEY BE OPERATED?
  
 7C) IN THE EVENT THEY FAIL, HOW WILL A PERSON BE ABLE
 TO GET EXIT OUT?
  
 7D) AS A DOOR WITHIN EXIT ACCESS, UNDER WHAT CODE
 WITHIN NFPA 101, CH 7, MEANS OF EGRESS ARE THEY IN
 COMPLIANCE WITH?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND SPECIFIC CODE
 REFERENCES.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL