| 2019-05-15 09:50:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A .01 - UNDER MEANS OF EGRESS;A, C & D, THERE |
| | ARE CODE REFERENCES OF NFPA 101, CH 38. NEW BUSINESS |
| | OCCUPANCIES. |
| | |
| | THIS OCCUPANCY IS STORAGE/S1. |
| | |
| | PLEASE REVIEW AND CORRECT THE CODE REFERNCES. |
| | |
| | |
| | |
| | 2) SHEET 0.1 COV & A1.0 - FOR CLARIFICATION PURPOSES, |
| | EVEN IF THERE IS EXISITNG FIRE SPRINKLER PROTECTION |
| | WITHIN ANY OF THE BUILDINGS THE EXTENT OF THE SPRINKLER |
| | DESIGN REQUIRES F.A.C. 61G DOCUMENTS WITH THIS MASTER |
| | PERMIT. |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTS IN ETHER PLAN |
| | DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY THE |
| | EOR.(SHOP DRAWINGS SHALL BE SUBMITED BASED ON THESE) |
| | (SHOULD THE EOR DEFER, A LETTER NEEDS TO BE SUBMITTED; |
| | HOWEVER, THE DEFERRED EOR WILL NEED TO SUBMIT 61 G |
| | DOCUMENTS WITH THE MASTER) |
| | |
| | PLEASE REVIEW AND PROVIDE WITH THIS MASTER |
| | |
| | |
| | |
| | 3) SHEET A 1.1 - THERE ARE INDICATIONS OF THE |
| | RELOCATION OF THE FIRE RISER WHICH MAY INCLUDE |
| | UNDERGROUND FIRE LINE WORK. |
| | |
| | ALL UNDERGROUND FIRE LINE WORK SHALL BE DONE IN |
| | COMPLIANCE WITH NFPA 24 UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A APPLICABLE NOTE. |
| | |
| | |
| | |
| | 4) SHEET A 1.1 - THERE ARE INDICATIONS OF THE |
| | RELOCATION OF THE FIRE RISER AND TO REFER TO THE CIVIL |
| | DRAWINGS. |
| | |
| | THERE ARE NO CIVIL DRAWINGS ATTACHED OR REFERENCED ON |
| | THE COVER SHEET. |
| | |
| | PLEASE REVIEW AND PROVIDE |
| | |
| | |
| | |
| | 5) SHEET A 1.1 - THERE ARE NO INDICATIONS OF THE |
| | LOCATION OF EXISITNG OR PROPOSED FIRE HYDRANT LOCATIONS |
| | OR AND CIVIL DRAWINGS TO REFER TO. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | 6) SHEET E 9 - THERE DOES NOT APPEAR TO BE ANY EXIT |
| | LIGHTS OR EMERGENCY LIGHTS WITHIN THE CORRIDOR OF BLDG |
| | D. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 7) SHEET DE 1.1 - THERE ARE ROLL-UP DOORS INDICATED |
| | WITH THE NUMBER 21 THAT APPEAR TO BE AT THE ONLY |
| | ENTRANCE/EXIT TO THE INTERNAL CORRIDORS. |
| | |
| | 7A) AS THESE DOORS ARE EXITS, HOW WILL THEY BE SECURED |
| | IN PLACE? |
| | |
| | 7B) HOW WILL THEY BE OPERATED? |
| | |
| | 7C) IN THE EVENT THEY FAIL, HOW WILL A PERSON BE ABLE |
| | TO GET EXIT OUT? |
| | |
| | 7D) AS A DOOR WITHIN EXIT ACCESS, UNDER WHAT CODE |
| | WITHIN NFPA 101, CH 7, MEANS OF EGRESS ARE THEY IN |
| | COMPLIANCE WITH? |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |