| 2019-06-12 06:48:25 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040656 |
| | ADD: 516 MONCEAUX ROAD |
| | CONT: MANGONE SONS CONSTRUCTION COMPANY |
| | TEL: 954-520-8554 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY: JUNE 10/2019 |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE NOTE THE PLANS FOR ALL BUILDINGS ON ONE SET |
| | OF PRINTS IS OK, BUT A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR WORK ON EACH BUILDING. PLEASE FILE OUT 4 MORE |
| | PERMITS FOR THE MAIN BUILDING PERMIT FOR EACH BUILDING. |
| | IDENTIFY WHICH BUILDING THE PERMIT APPLIED FOR WILL BE |
| | ASSOCIATED WITH. SEPARATE PERMITS ARE REQUIRED FOR |
| | RECORD KEEPING OF INSPECTIONS FOR EACH BUILDING AND FOR |
| | RECORD RETENTION PURPOSES AS WELL FOR CERTIFICATE OF |
| | OCCUPANCIES. |
| | 107.2.1.3 QUALITY OF BUILDING PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | |
| | 1B) WITH THE 5 SEPARATE BUILDING PERMITS FOR THE 5 |
| | STRUCTURES PLEASE BREAK OUT THE ORIGINAL VALUE |
| | ($5,400,000.00) FOR THE PROJECT AND ASSIGN THE VALUE OF |
| | DOLLARS FOR THE SCOPE OF WORK ASSOCIATED WITH EACH |
| | BUILDING. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 3A) THE COVERSHEET DOES NOT PROVIDE A SURVEY AS PART OF |
| | THE PERMIT PACKAGE GIVING THE EXISTING BUILDINGS |
| | LOCATION ON THE LOT, CLOSENESS TO THE PROPERTY LINE, |
| | NOR THE PROPOSED LOCATION FOR BUILDINGS D & E. THE |
| | COVERSHEET DOES LIST A CIVIL ENGINEER SIMMONS & WHITE |
| | BUT THERE IS NO CIVIL PLANS SUBMITTED UNDER THIS REVIEW |
| | EITHER. ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY/ SET BACK/ SEPARATION/ ASSUMED PROPERTY LINES |
| | BETWEEN BUILDINGS |
| | FBC-B TABLE 602 S-1 2 HR. EXTERIOR WALLS |
| | FBC-B TABLE 705.8 DOOR AND WINDOW UNPROTECTED/ |
| | NON-SPRINKLERED BUILDING |
| | |
| | |
| | 3B) THE DESIGNER OF RECORD HAS PROVIDED A BUILDING KEY |
| | PLAN ON THE COVERSHEET FOR BUILDINGS D & E AND THE |
| | FLOOR PLANS DE-1.0 BUILDING E AND DE-1.1 FOR BUILDING D |
| | BUT THERE ARE NO DIMENSIONS BETWEEN BUILDINGS SHOWING |
| | AN ASSUMED PROPERTY LINE FOR COMPLIANCE WITH TABLE 602 |
| | FIRE RESISTANCE RATINGS FOR EXTERIOR WALLS BASED ON |
| | FIRE SEPARATION DISTANCE NOR TABLE 705.8 OPENING |
| | PROTECTIVES BASED ON FIRE SEPARATION DISTANCE OF T THE |
| | 2017 FBC-B. |
| | |
| | 3C) SHEET 043-S1.0 BUILDING A SHOWS A NEW TOWER FEATURE |
| | ON THE NORTH SIDE OF THE BUILDING, BUT THERE WAS NO |
| | SURVEY SHOWING IF THE FOUNDATION AND TOWER ENCROACHES |
| | BEYOND THE LOT LINE. 2017 FBC-B 3202.1.1. |
| | |
| | 4) MISSING FROM THIS REVIEW CYCLE IS THE GEOLOGICAL |
| | REPORT PREPARED BY GFA INTERNATIONAL PROJECT # |
| | 18-0101.00 DATED 12/04/2018 AS STATED IN SHEET 040-S0.0 |
| | GENERAL NOTE 1 UNDER EARTHWORK? |
| | |
| | 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 5A) THE PLANS ARE ALSO LACKING ENERGY COMPLIANCE |
| | REPORTS. SEE THE 2017 FBC-ENERGY SECTION C401.2 |
| | APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 5.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, |
| | EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD. |
| | 5.2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | 5.3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| | OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 5B) 2017 FBC-EXISTING BUILDING CODE 1106.1 ADDITIONS TO |
| | EXISTING BUILDINGS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, ENERGY CONSERVATION. |
| | |
| | 6) THE COVERSHEET UNDER THE HEADING BUILDING & CODE |
| | INFORMATION STATES BUILDINGS A-C ARE FULLY SPRINKLERED |
| | BUT YET ON BUILDING B A SECOND STORY IS BEING ADDED AND |
| | ON BUILDING 3 2 STORIES ARE BEING ADDED. NO FIRE |
| | SPRINKLER PLANS WERE SUBMITTED IN THIS PACKAGE. IN THE |
| | 2017 FBC-EXISTING BUILDING CODE UNDER CHAPTER 11 |
| | ADDITIONS SECTION 1102.3 DEALS WITH FIRE PROTECTION |
| | SYSTEMS. EXISTING FIRE AREAS INCREASED BY ADDITIONS |
| | SHALL COMPLY WITH CHAPTER 9 OF THE FBC-B. EXCEPTIONS: |
| | IF AN EXISTING WAREHOUSE IS EXPANDED, THE ADDITION MUST |
| | COMPLY WITH THE REQUIREMENTS IN CHAPTER 9 OF THE FBC-B, |
| | HOWEVER THE EXISTING WAREHOUSE NEED NOT UPDATED TO MEET |
| | THOSE REQUIREMENTS SO LONG AS IT IS IN COMPLIANCE WITH |
| | THE FBC-B 2001 EDITION, AND WITH THE REQUIREMENTS |
| | CONCERNING AUTOMATIC SPRINKLERS IN SECTION 903 OF THE |
| | FBC-B. |
| | |
| | 6A) EXISTING BUILDING B THE EXISTING 1ST FLOOR LEVEL |
| | INDICATES A SQUARE FEET OF FIRE AREA OF 36,700 SQ. FT. |
| | OVER THE COMBINED AREAS OF ALL GROUP S-1 FIRE AREAS ON |
| | ALL FLOORS EXCEEDS 24, 000 SQ. FT. SEE 2017 FBC-B |
| | 903.2.9 (3) & (5). REQUIRING FIRE SPRINKLERS. |
| | |
| | 6B) EXISTING BUILDING C THE EXISTING 1ST FLOOR LEVEL |
| | INDICATES A SQUARE FEET OF FIRE AREA OF 30,000 SQ. FT. |
| | WITH THE PROPOSED ADDITIONS THE TOTAL SQ. FT. IS 91,956 |
| | SQ. FT. OVER THE COMBINED AREAS OF ALL GROUP S-1 FIRE |
| | AREAS ON ALL FLOORS EXCEEDS 24, 000 SQ. FT. SEE 2017 |
| | FBC-B 903.2.9 (3) & (5). REQUIRING FIRE SPRINKLERS. |
| | |
| | 6C) W. P. B. ADMINISTRATIVE CODE105.3.1.2 (2) FIRE |
| | SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION |
| | WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS |
| | 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR |
| | II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, |
| | FLORIDA STATUTES, MAY DESIGN A FIRE |
| | SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN |
| | THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF |
| | THE ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR |
| | DELETION OF NOT MORE THAN 49 HEADS, NOTWITHSTANDING THE |
| | SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM. |
| | |
| | FIRE SPRINKLERS 61G15-32.004 DESIGN OF WATER BASED FIRE |
| | PROTECTION SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: (A-M). |
| | |
| | 6D) PLEASE PROVIDE HYDRAULIC CALCULATIONS SHOWING THE |
| | EXISTING MAIN CAN TAKE THE ADDITIONAL LOAD OF THE |
| | VERTICAL ADDITIONS TO THE EXISTING FIRE SPRINKLER |
| | SYSTEM, 2017 FBC-B 903.3.8.5. |
| | |
| | 7) SHEET A-10 HAS A NOTE THAT ALL VERTICAL CONDUIT |
| | RISERS FOR POSSIBLE RADIO PROPAGATION SIGNAL |
| | AMPLIFICATION SHALL BE WITHIN A 2 HOUR FIRE RATED |
| | PARTITION ENCLOSURE IN ACCORDANCE WITH UL # U419 |
| | ASSEMBLY. PLEASE PROVIDE WHERE THIS 2 HOUR FIRE BARRIER |
| | IS TO BE BUILT. 2017 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED. |
| | |
| | 8) THE LIFE SAFETY SHEET 003-A-0.1 DESIGNATES BLDGS. A, |
| | B, & C. THE COVERSHEET UNDER THE HEADING OF AREA |
| | CALCULATIONS LIST EACH BUILDING AND FIRE AREA PER FLOOR |
| | PER BUILDING. IT WOULD APPEAR THE FIRE WALLS THAT |
| | SEPARATE EACH OF THE BUILDINGS FOR ANOTHER WOULD APPEAR |
| | ON THE LIFE SAFETY PLAN. PLEASE PROVIDE WHERE THE FIRE |
| | WALL LOCATIONS OCCUR AND THE RATING OF THE FIRE WALL IN |
| | ACCORDANCE TO TABLE 706.4 OF THE 2017 FBC- |
| | B. THIS SAME FIRE RATING OF THE FIRE WALLS SHOULD ALSO |
| | OCCUR ON ALL FLOOR PLANS FOR BUILDING A, B & C. |
| | |
| | 8A) SHEET 004-A-1.0 DOES NOT SHOW THE FIRE WALLS DOOR # |
| | 13 IS WITHIN THE FIRE WALL BUT THE DOOR SCHEDULE ON |
| | SHEET A1.10 DOES NOT SHOW A FIRE RATING AS REQUIRED BY |
| | TABLE 716.5 OF THE 2017 FBC-B. THE SAME HOLDS TRUE FOR |
| | DOOR 13. |
| | |
| | 8B) SHEET 004-A-1.0 SHOWS A RAMP 1/12 AT THE BOTTOM OF |
| | THE PAGE THERE IS A HASHED LINE FOR AN ENLARGED DETAIL |
| | AND A STATEMENT SEE SHEET A-XXX FOR ENLARGED VIEW AND |
| | ADDITIONAL INFORMATION. PLEASE PROVIDE DETAIL FOR |
| | ACCESSIBLE RAMP, HANDRAILS AND RECEPTION COUNTER HEIGHT |
| | FOR ACCESSIBLE ELEMENTS. 2017 FBC-ACCESS. CODE RAMPS |
| | 405, AND 904SALES AND SERVICE COUNTERS. |
| | |
| | 8C) THERE IS A SECOND NOTE IN THE SAME DETAIL TO REFER |
| | TO SITE PLAN BY OTHERS FOR ALL EXTERIOR SITE WORK. NOTE |
| | THERE IS NO SITE PLAN OR CIVIL PLANS IN THE SUBMITTED |
| | SET OF PLANS. ACCESSIBILITY FROM THE SITE ARRIVAL POINT |
| | CANNOT BE CHECKED ACCESS. CODE 206.2.1, TO ACCESSIBLE |
| | PARKING (ACCESS. CODE 208.2, 502.2 VEHICLE SPACES), |
| | ACCESS AISLE (ACCESS. CODE 502.3) TO ENTRY POINT OF THE |
| | BUILDING CANNOT BE VERIFIED. |
| | |
| | 8D) THE PLANS DO NOT INDICATE THE TOTAL AMOUNT OF |
| | STORAGE UNITS ARE AVAILABLE, HOW MANY UNITS OF EACH |
| | SIZE, AND IF AIR CONDITIONED OR NOT. PLEASE PROVIDE A |
| | MATRIX SHOWING COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTIONS: |
| | |
| | 8D)(1) 225.3 SELF-SERVICE STORAGE FACILITIES. |
| | SELF-SERVICE STORAGE FACILITIES SHALL PROVIDE |
| | INDIVIDUAL SELF- SERVICE STORAGE SPACES COMPLYING WITH |
| | THESE REQUIREMENTS IN ACCORDANCE WITH TABLE 225.3. |
| | ADVISORY 225.3 SELF-SERVICE STORAGE FACILITIES. |
| | ALTHOUGH THERE ARE NO TECHNICAL REQUIREMENTS THAT ARE |
| | UNIQUE TO SELF-SERVICE STORAGE FACILITIES, ELEMENTS AND |
| | SPACES PROVIDED IN FACILITIES CONTAINING SELF-SERVICE |
| | STORAGE SPACES REQUIRED TO COMPLY WITH THESE |
| | REQUIREMENTS MUST COMPLY WITH THIS CODE WHERE |
| | APPLICABLE. FOR EXAMPLE: THE NUMBER OF STORAGE SPACES |
| | REQUIRED TO COMPLY WITH THESE REQUIREMENTS MUST PROVIDE |
| | ACCESSIBLE ROUTES COMPLYING WITH SECTION 206; |
| | ACCESSIBLE MEANS OF EGRESS COMPLYING WITH SECTION 207; |
| | PARKING SPACES COMPLYING WITH SECTION 208; AND, WHERE |
| | PROVIDED, OTHER PUBLIC USE OR COMMON USE ELEMENTS AND |
| | FACILITIES SUCH AS TOILET ROOMS, DRINKING FOUNTAINS, |
| | AND TELEPHONES MUST COMPLY WITH THE APPLICABLE |
| | REQUIREMENTS OF THIS CODE. |
| | |
| | 8D)(2) 225.3.1 DISPERSION. INDIVIDUAL SELF-SERVICE |
| | STORAGE SPACES SHALL BE DISPERSED THROUGHOUT THE |
| | VARIOUS CLASSES OF SPACES PROVIDED. WHERE MORE CLASSES |
| | OF SPACES ARE PROVIDED THAN THE NUMBER REQUIRED TO BE |
| | ACCESSIBLE, THE NUMBER OF SPACES SHALL NOT BE REQUIRED |
| | TO EXCEED THAT REQUIRED BY TABLE 225.3. SELF-SERVICE |
| | STORAGE SPACES COMPLYING WITH TABLE 225.3 SHALL NOT BE |
| | REQUIRED TO BE DISPERSED AMONG BUILDINGS IN A |
| | MULTI-BUILDING FACILITY. |
| | |
| | 8E) SHEET 004-A-1.0 & 005-A1.1 NEW ENTRY FOR BUILDING B |
| | SHOWS DOOR # 10 IN THE NEW STAIR TOWER. SHEET A-1.10 |
| | THE DOOR SCHEDULE INDICATES DOOR # 10 AS A C LABEL FIRE |
| | DOOR. PLEASE NOTE IN THE 2017 FBC-B TABLE 716.5 LIST |
| | THE RATINGS OF FIRE RATING OF DOORS IN HOURS OR |
| | PORTIONS OF HOURS. PLEASE CORRECT. |
| | |
| | 9) SHEET 005-A1.1 THERE IS A NOTE ON THE WEST SIDE OF |
| | THE BUILDING THAT THE FIRE WATER SUPPLY RISER IS TO BE |
| | REMOVED AND RELOCATED. A 2ND NOTE INDICATES THE NEW |
| | FIRE WATER SUPPLY PIPE RISER LOCATION, REFER TO CIVIL |
| | PLANS. NO CIVIL PLANS WERE SUBMITTED FOR THIS REVIEW. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 9A) PLEASE NOTE SHEET 005-A1.1 IS THE SOUTH END OF |
| | BUILDING B, AND AT GRID LINE 21 THIS IS THE COMMON |
| | PARTY WALL BETWEEN BUILDING B & BUILDING C. ON BOTH THE |
| | 1ST AND 2ND FLOOR THERE IS AN OPENING BETWEEN THE 2 |
| | BUILDINGS IN THE 3 HOUR FIRE WALL. THE PLANS DO NOT |
| | SHOW EITHER A FIRE DOOR OR FIRE SHUTTER. SHOW |
| | COMPLIANCE WITH 2017 FBC-B TABLE 716.5. PLEASE ALSO |
| | NOTE ON SHEET 003-A-0.1 THE 1ST FLOOR OF THE LIFE |
| | SAFETY PLAN AT THIS SAME LOCATION IT SHOWS THIS AREA AS |
| | AN EXIT? IF THIS IS TO BE AN EXIT WHICH SIDE OF THE |
| | FIRE DOOR IS THE EXIT TO BE LOCATED? WILL THIS DOOR BE |
| | A 3 HOUR FIRE DOOR OR 2 FIRE DOORS WITH BOTH HAVING AN |
| | 1 ? HOUR FIRE RATING, SEE TABLE 716.5 FOOTNOTE A. |
| | |
| | 9B) PLEASE ALSO CONSIDER THE OPENING (FIRE DOOR) |
| | BETWEEN BUILDING B & C ALSO NEEDS TO HAVE 18 INCHES ON |
| | THE LATCH SIDE OF THE DOOR FOR MANEUVERING CLEARANCES. |
| | 2017 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 2017 ACCESS. CODE 404.2.4. |
| | MANEUVERING CLEARANCES SHALL EXTEND THE FULL WIDTH OF |
| | THE DOORWAY AND THE REQUIRED LATCH SIDE FOR SIDE |
| | CLEARANCE. |
| | |
| | 9C) ON BOTH THE ARCHITECTURAL SHEET 005-A-1.1 AND THE |
| | STRUCTURAL SHEET 046-S1.3 THERE IS A NOTE # 6 |
| | PRE-ENGINEERED WALLS (BEARING) ON DECK TO BE DESIGNED |
| | BY A LICENSED FLORIDA PROFESSIONAL ENGINEER. |
| | CALCULATIONS AND SHOP DRAWINGS TO BE SIGNED AND SEALED |
| | AND SUBMITTED TO THE ARCHITECT FOR REVIEW. PLEASE BE |
| | AWARE OF THE RESPONSIBILITIES OF THE STRUCTURAL |
| | ENGINEER OF RECORD THAT MUST ALSO APPLY THEIR SHOP |
| | DRAWING STAMP OF APPROVAL ON ALL CALCULATIONS AND SHOP |
| | DRAWINGS. |
| | 61G15-31.001 GENERAL RESPONSIBILITY. THE ENGINEER OF |
| | RECORD IS RESPONSIBLE FOR ALL STRUCTURAL ASPECTS OF THE |
| | DESIGN OF THE STRUCTURE INCLUDING THE DESIGN OF ALL OF |
| | THE STRUCTURE?S SYSTEMS AND COMPONENTS. AS NOTED HEREIN |
| | THE ENGINEER OF RECORD MAY DELEGATE RESPONSIBILITY FOR |
| | THE DESIGN OF A SYSTEM OR COMPONENT PART OF THE |
| | STRUCTURE TO A DELEGATED ENGINEER. IN EITHER CASE THE |
| | STRUCTURAL ENGINEERING DOCUMENTS SHALL ADDRESS, AS A |
| | MINIMUM, THE ITEMS NOTED IN THE FOLLOWING SUBSECTIONS |
| | COVERING SPECIFIC STRUCTURAL SYSTEMS OR COMPONENTS. THE |
| | ENGINEER OF RECORD?S STRUCTURAL ENGINEERING DOCUMENTS |
| | SHALL IDENTIFY DELEGATED SYSTEMS AND COMPONENTS. BOTH |
| | THE ENGINEER OF RECORD FOR THE STRUCTURE AND THE |
| | DELEGATED ENGINEER, IF UTILIZED, SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE GENERAL RESPONSIBILITY RULES, |
| | CHAPTER 61G15-30, F.A.C., AND WITH THE REQUIREMENTS OF |
| | THE MORE SPECIFIC STRUCTURAL RESPONSIBILITY RULES |
| | CONTAINED HEREIN. THE ENGINEER OF RECORD FOR THE |
| | STRUCTURAL SYSTEM(S) SHALL PROVIDE DESIGN REQUIREMENTS |
| | IN WRITING TO THE DELEGATED ENGINEER IF ONE IS USED AND |
| | SHALL REVIEW THE DESIGN DOCUMENTS OF THE DELEGATED |
| | ENGINEER FOR CONFORMANCE WITH HIS WRITTEN INSTRUCTIONS |
| | IN ACCORDANCE WITH RULE 61G15-30.005, F.A.C. WHEN |
| | INFORMATION COLLECTED FROM THE ENGINEER OR THE |
| | ENGINEER?S AUTHORIZED REPRESENTATIVE FROM A SITE VISIT |
| | IS PART OF THE ENGINEER?S DELIVERATIVE PROCESS, THE |
| | ENGINEER IS RESPONSIBLE FOR THE ACCURACY OF SUCH |
| | INFORMATION. |
| | |
| | 10A) SHEET 003-A-0.1 LIFE SAFETY, A-1.0, A-1.1 & A- |
| | 1.2. WITHOUT THE BENEFIT OF SEEING THE SOILS |
| | ENGINEERING REPORT, PLEASE RESPONSE ABOUT THE CLOSENESS |
| | OF THE ELEVATOR PITS AND THE RECESSED TRUCK WELL WITH |
| | THE FOUNDATION OF THE EXISTING BUILDING. PLEASE SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 1804.1. |
| | EXCAVATIONS NEAR FOUNDATIONS. |
| | |
| | 10B) SHEET 006-A-1.2 SECTION A SHOWS THE RECESSED TRUCK |
| | WELL AND A NOTE THAT TRUCK WELL VARIES IN DEPTH FROM |
| | 0-48 INCHES IN DEPTH. THE PLAN ALSO SHOWS A GUARDRAIL |
| | AT 42 INCHES HIGH WITH INTERMEDIATE HORIZONTAL RAILINGS |
| | AT 12 INCHES ON CENTER. SINCE THIS IS A SELF STORAGE |
| | FACILITY THE GENERAL PUBLIC WOULD BE ABLE TO USE THE |
| | RECESSED TRUCK WELL, SHOW COMPLIANCE WITH FBC-B 1015.4 |
| | OPENING LIMITATIONS WHERE GUARDS SHALL NOT ALLOW THE |
| | PASSAGE OF A 4 INCH SPHERE. |
| | |
| | 10C) SHEET 006-A-1.2 SECTION THROUGH THE STAIRWELL |
| | 1/A-3.5 THIS DETAIL INDICATES THEY WILL BE A |
| | PREFABRICATED METAL STAIR. WHAT THE PLAN DOES NOT TELL |
| | US IS IF THE RISERS ARE SOLID. SINCE THIS IS A |
| | SELF-STORAGE FACILITY THE PUBLIC WILL BE USING THE |
| | STAIRS. PLEASE PROVIDE COMPLIANCE WITH FBC-B 1011.5.5.3 |
| | SOLID RISERS. |
| | |
| | 10D) SHEET 006-A-1.2 SECTION THROUGH THE STAIRWELL |
| | 1/A-3.5 THIS DETAIL INDICATES THEY WILL BE A |
| | PREFABRICATED METAL STAIR. PLEASE SHOW HOW COMPLIANCE |
| | WITH VERTICAL CLEARANCE OF THE FBC-ACCESS. CODE SECTION |
| | 307.4 AND FIGURE 307.4 WILL BE MAINTAINED. |
| | |
| | 11) SHEET 007-A-1.3 THE NEW LOADING DOCK ROOF IS SHOWN |
| | AS A LOW SLOPED ROOF, SHEET 018-A-3.2 SHOWS A PARAPET |
| | WALL SURROUNDING A HIPPED ROOF ON 3 SIDES. SHEET A-1.3 |
| | INDICATES THE USE OF 2 ROOF DRAINS THE SIZE NOT GIVEN |
| | AND 2 / 4 INCH OVER FLOW ROOF DRAINS. THE ROOF DRAINAGE |
| | IS TO BE SIZED TO THE 100 YEAR, 1 HOUR RAINFALL FOR THE |
| | AREA OF THE BUILDING BEING BUILT LOCATION. FBC-B 1503.4 |
| | ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO DRAIN OVER |
| | ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE |
| | SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE FLORIDA |
| | BUILDING CODE, PLUMBING, CHAPTER 11. |
| | |
| | 12) SHEET 018-A3.2 SECTION 1 INDICATES ROOF TOP |
| | MECHANICAL EQUIPMENT BEING SET AT 2 FEET TO THE BOTTOM |
| | OF THE A/C UNIT ABOVE THE FLAT ROOF. THERE IS A |
| | HORIZONTAL STEEL FRAMING MEMBER BELOW THE EQUIPMENT, |
| | THAT CLEAR SPACE IS NOT GIVEN. PLEASE REVIEW IN THE |
| | 2017 FBC-B SECTION 1510.10 AND TABLE 1510.10 FOR THE |
| | MINIMUM VERTICAL CLEARANCES REQUIRED DEPENDING ON THE |
| | WIDTH OF THE UNIT. |
| | |
| | 13) PLEASE REVIEW SHEET 033-DE-3.1 BOTH WALL SECTIONS |
| | SHOW THE TOP OF THE FOOTING A MINIMUM OF 8 INCHES BELOW |
| | GRADE. PLEASE REVIEW SECTION 1809.4 THE MINIMUM DEPTH |
| | OF FOOTINGS. 2017 FBC-B THE MINIMUM DEPTH OF FOOTINGS |
| | BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12 |
| | INCHES. |
| | |
| | 14) SHEET 028-DE-1.1 INDICATES THE INTERIOR FIRE WALLS |
| | SHALL BE TIGHT TO AND FOLLOW THE RAKE OF THE ROOF |
| | PANELS. ON THE SAME SHEET DETAIL A/ DE-32 IS GIVEN. IN |
| | THIS DETAIL THE NOTE STATES PRE-ENGINEERED STEEL WALL |
| | AND ROOF DESIGN, BUT IN EITHER CASE IS THERE A WALL |
| | IDENTIFICATION TAG, IDENTIFYING THE REQUIRED 3 HOUR |
| | FIRE WALL REQUIRED UNDER THE 2017 FBC-B SECTION |
| | 707.3.10 AND TABLE 707.3.10. |
| | |
| | 15A) SHEET 029-DE-1.2 THE SOUTH PROPERTY LINE WALL |
| | SHOWS A CUT SECTION 2/ DE3.2. THIS DETAIL DOES NOT |
| | PROVIDE IF THERE IS ANY WALL RATINGS REQUIRED, BECAUSE |
| | THE CLOSENESS TO THE PROPERTY LINE. THE 2017 FBC-B |
| | TABLE 602 REQUIRES A 2 HOUR FIRE RATED WALL IF LESS |
| | THAN 5.0 FEET FROM THE PROPERTY LINE. SHEET 027-DE-1.0 |
| | DOES HAVE A NOTE THAT ALL PROPERTY LINE MASONRY WALLS |
| | SHALL HAVE A 2 HOUR RATING PER UL U905. THE BLOCK |
| | MANUFACTURER WILL NEED TO SUPPLY A LETTER AS TO WHICH |
| | BLOCK THEY MAKE WILL HAVE AN EQUIVALENT THICKNESS, TYPE |
| | OF AGGREGATE FOR A 2 HOUR FIRE RATED BLOCK. SEE FBC-B |
| | TABLE 722.3.2. |
| | |
| | 15B) THIS SAME SHEET THERE IS ANOTHER CUT SECTION |
| | THROUGH THE SOUTH PROPERTY LINE WALL, SECTION 2/DE-3.3. |
| | THIS DETAIL DOES NOT PROVIDE IF THERE IS ANY WALL |
| | RATINGS REQUIRED, BECAUSE THE CLOSENESS TO THE PROPERTY |
| | LINE. THE 2017 FBC-B TABLE 602 REQUIRES A 2 HOUR FIRE |
| | RATED WALL IF LESS THAN 5.0 FEET FROM THE PROPERTY |
| | LINE. THIS DETAIL DOES NOT PROVIDE IF THERE IS ANY WALL |
| | RATINGS REQUIRED, BECAUSE THE CLOSENESS TO THE PROPERTY |
| | LINE. THE 2017 FBC-B TABLE 602 REQUIRES A 2 HOUR FIRE |
| | RATED WALL IF LESS THAN 5.0 FEET FROM THE PROPERTY |
| | LINE. |
| | |
| | 16) SHEET 034-DE-3.2 WALL SECTION 4 SHOWS FOR ALL OF |
| | THE DOORS IN BUILDINGS D & E TO BE ROLL- UP TYPE DOORS. |
| | THE ROLL UP DOOR IS THE ONLY MEANS OF EGRESS OUT OF ANY |
| | STORAGE UNIT. IN THE 2017 FBC-B THE CODE GIVES AN |
| | EXCEPTION TO THE REQUIRED EGRESS DOORS BEING REQUIRED |
| | TO BE A SIDE-SWING OR PIVOTING DOOR. EXCEPTION 1 ALLOWS |
| | FOR OFFICE AREAS, FACTORY AND STORAGE AREAS WITH AN |
| | OCCUPANT LOAD OF 10 OR LESS. 2017 FBC-B TABLE 1004.1.2 |
| | FOR WAREHOUSES THE OCCUPANT LOAD FACTOR IS TAKEN AT 500 |
| | GROSS. WHERE A UNIT HAS 20X8= 160 SQ. FT. OR AN |
| | OCCUPANT LOAD OF 1. THE FIRE PREVENTION CODE MAY HAVE A |
| | MORE STRINGENT CODE. WHEN THERE IS A DIFFERENCE BETWEEN |
| | THE 2 CODES THE MOST STRINGENT CODE PREVAILS. |
| | |
| | 17) SHEETS DE1.1 & DE 1.2 BOTH SHOW A ROOFING SYSTEM |
| | LAYOUT. SHEET 034-DE-3.2 ALL DETAILS SHOW A |
| | PRE-ENGINEERED STANDING SEAM METAL ROOD SYSTEM. WHAT IS |
| | A UNKNOWN IS IF THIS ROOF SYSTEM HAS FOAM INSULATION |
| | INNER CORE, PLANS REALLY NEED ADDITIONAL INFORMATION IN |
| | THIS AREA. THERE IS ALSO A NOTE THAT THERE WILL ALSO BE |
| | PRE-ENGINEERED PURLINS AT 5 FEET ON CENTER. THE DETAILS |
| | ALSO INDICATE GALVALUME STEEL PARTITION PANELS, SEE |
| | PRE-ENGINEERED DRAWINGS AND PRE-ENGINEERED CEE CHANNEL |
| | COLUMNS SEE PRE-ENGINEERED DRAWINGS. PLANS BY OTHERS |
| | FOR ALL DETAILS FOR INTERIOR WALLS AND ROOF FRAMING FOR |
| | ALL SINGLE STORY BUILDINGS. |
| | BUILDINGS D & E ARE DESIGNED AS CONSTRUCTION TYPE II-B. |
| | PLEASE NOTE IF THE ROOFING STANDING SEAM DOES HAVE AN |
| | INNER FOAM CORE, THAT FOAM CORE WOULD HAVE TO COMPLY |
| | WITH THE TYPE OF CONSTRUCTION FOR A TYPE II-B |
| | STRUCTURE. |
| | 2017 FBC-B 602.2 TYPES I AND II. TYPES I AND II |
| | CONSTRUCTION ARE THOSE TYPES OF CONSTRUCTION IN WHICH |
| | THE BUILDING ELEMENTS LISTED IN TABLE 601 ARE OF |
| | NONCOMBUSTIBLE MATERIALS, EXCEPT AS PERMITTED IN |
| | SECTION 603 AND ELSEWHERE IN THIS CODE. |
| | DELEGATE ENGINEERING. 61G15-31.001 GENERAL |
| | RESPONSIBILITY. THE ENGINEER OF RECORD IS RESPONSIBLE |
| | FOR ALL STRUCTURAL ASPECTS OF THE DESIGN OF THE |
| | STRUCTURE INCLUDING THE DESIGN OF ALL OF THE |
| | STRUCTURE?S SYSTEMS AND COMPONENTS. AS NOTED HEREIN THE |
| | ENGINEER OF RECORD MAY DELEGATE RESPONSIBILITY FOR THE |
| | DESIGN OF A SYSTEM OR COMPONENT PART OF THE STRUCTURE |
| | TO A DELEGATED ENGINEER. IN EITHER CASE THE STRUCTURAL |
| | ENGINEERING DOCUMENTS SHALL ADDRESS, AS A MINIMUM, THE |
| | ITEMS NOTED IN THE FOLLOWING SUBSECTIONS COVERING |
| | SPECIFIC STRUCTURAL SYSTEMS OR COMPONENTS. THE ENGINEER |
| | OF RECORD?S STRUCTURAL ENGINEERING DOCUMENTS SHALL |
| | IDENTIFY DELEGATED SYSTEMS AND COMPONENTS. BOTH THE |
| | ENGINEER OF RECORD FOR THE STRUCTURE AND THE DELEGATED |
| | ENGINEER, IF UTILIZED, SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE GENERAL RESPONSIBILITY RULES, |
| | CHAPTER 61G15-30, F.A.C., AND WITH THE REQUIREMENTS OF |
| | THE MORE SPECIFIC STRUCTURAL RESPONSIBILITY RULES |
| | CONTAINED HEREIN. THE ENGINEER OF RECORD FOR THE |
| | STRUCTURAL SYSTEM(S) SHALL PROVIDE DESIGN REQUIREMENTS |
| | IN WRITING TO THE DELEGATED ENGINEER IF ONE IS USED AND |
| | SHALL REVIEW THE DESIGN DOCUMENTS OF THE DELEGATED |
| | ENGINEER FOR CONFORMANCE WITH HIS WRITTEN INSTRUCTIONS |
| | IN ACCORDANCE WITH RULE 61G15-30.005, F.A.C. WHEN |
| | INFORMATION COLLECTED FROM THE ENGINEER OR THE |
| | ENGINEER?S AUTHORIZED REPRESENTATIVE FROM A SITE VISIT |
| | IS PART OF THE ENGINEER?S DELIVERATIVE PROCESS, THE |
| | ENGINEER IS RESPONSIBLE FOR THE ACCURACY OF SUCH |
| | INFORMATION. |
| | |
| | 18) SHEET 030-DE-2.0 SHOWS THE TYPICAL END ELEVATION |
| | AND WHAT APPEARS TO BE THE INTERIOR WALL ZONE A) AND |
| | END ZONE (B). NO MENTION OF THE PRESSURES (+/-). SHEET |
| | 040-S0.0 THE WIND DESIGN CRITERIA IS PROVIDED. |
| | THE SHEET 040-S-0.0 GAVE THE WIND DESIGN CRITERIA BUT |
| | NOT THE PRESSURES FOR ROOF ZONES 1, 2, AND 3 NOR THE |
| | WALL ZONES 4 AND 5. NOT FOR THE 3 STORY BUILDING NOR |
| | FOR THE SINGLE STORY BUILDING. 5. DESIGN WIND PRESSURES |
| | TO BE USED FOR EXTERIOR COMPONENTS AND CLADDING |
| | MATERIALS. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR |
| | HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. PLEASE PROVIDE THE PRESSURES IN VASD SINCE |
| | THE PRODUCT APPROVALS ARE ALSO IN VASD. PLEASE PROVIDE |
| | THE POSITIVE AND NEGATIVE PRESSURES IN 10 SQ. FT. 20 |
| | SQ. FT., 50 SQ. FT., 100 SQ. FT. EFFECTIVE WIND AREA. |
| | |
| | 19) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 20) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 21) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 22) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 23) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 24) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 25) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 26) RESIDENT INSPECTOR. 2017 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. THE |
| | BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| | OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| | MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. |
| | FORMS E-MAILED TO: [email protected] 7:19 AM |
| | |
| | FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT: KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | |
| | NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING RESIDENT |
| | INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP DRAWINGS |
| | (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT APPROVALS, |
| | TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED TO THE |
| | BUILDING DEPARTMENT. TWO REVIEWED SETS OF DOCUMENTS |
| | WILL BE RETURNED TO THE JOB SITE BEFORE ANY OF THE |
| | ABOVE ARE INSTALLED ON THE JOB. |
| | |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 27) IMPACT FEES - DIGITAL SUBMITTALS: |
| | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| | |
| | 28) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |