| 2019-05-03 12:54:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE ELECTRICAL PLANS SUBMITTED FOR TEMPORARY SERVICE |
| | UNDER PERMIT 19031013 ONLY SHOW 277/480 VOLT |
| | DISTRIBUTION. THIS TRAILER CALLS FOR A 120/240 VOLT |
| | SINGLE PHASE SERVICE. WHERE IS THIS BEING FED FROM? |
| | WHAT IS THE LOAD REQUIRED FOR THE TRAILER? WHAT SIZE |
| | CONDUCTORS WILL FEED THE TRAILER? WHAT IS THE GROUNDING |
| | FOR THE TRAILER? PROVIDE RISER DIAGRAM AND LOAD |
| | CALCULATION WITH CORRECTIONS. NEC 215.5, 220, 250; WPB |
| | FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |