| 2019-04-25 08:37:32 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.INDICATE ON THE PLAN THE BREAK ROOM SINK SHALL COMPLY |
| | WITH FBC ACC 606.2 606.2 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. EXCEPTIONS: 1.A PARALLEL |
| | APPROACH COMPLYING WITH 305 SHALL BE PERMITTED TO A |
| | KITCHEN SINK, IN A SPACE WHERE A COOK TOP OR |
| | CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET BARS.THE |
| | CLEAR FLOOR SPACE SHALL BE CENTERED ON THE SINK. |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 2. SHT A-102 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE |
| | FOR THE TOILET AND LAVATORY PER FBC ACC 606.2, 604.3.1 |
| | |
| | 3. SHT. A-102 SHOW DIMENSION OF THE WIDTH OF THE |
| | BATHROOM TO VERIFY COMPLIANCE WITH FBC ACC 606.2, |
| | 604.3.1 |
| | |
| | 4. TWO DRINKING FOUNTAINS ARE REQUIRED PER FBC ACC |
| | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING |
| | FOUNTAINS. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | EXCEPTIONS: 1.A SINGLE DRINKING FOUNTAIN WITH TWO |
| | SEPARATE SPOUTS THAT COMPLIES WITH THE REQUIREMENTS FOR |
| | PEOPLE WHO USE A WHEELCHAIR AND STANDING PERSONS SHALL |
| | BE PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE |
| | DRINKING FOUNTAINS. |
| | |
| | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 6.THE DEMO PLAN A-101 DOES NOT SHOW ANY EXITING |
| | BATHROOM NOTE ON THE PLUMBING PAGE INDICATE THAT THERE |
| | IS EXISTING PIPING PLEASE SHOW ON THE SANITARY AND |
| | WATER ISOMETRIC DRAWINGS EXISTING AND NEW PIPING. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |