2019-04-29 12:02:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040582
 4/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: IT APPEARS THAT THE EXHAUST SYSTEM THAT
 WILL BE OPERATED BY STARTUP/STOP PUSH BUTTONS IS NOT IN
 COMPLIANCE WITH SECTION 6.7.1 ASHRAE 170-2008 WHICH
 INDICATES THAT AIR DISTRIBUTION DESIGN SHALL MAINTAIN
 THE PRESSURE RELATIONSHIPS IN ALL MODES OF HVAC
 OPERATION. BASED ON THAT SECTION, THE EXHAUST SYSTEM
 WILL HAVE TO OPERATE CONTINOUSLY TO MAINTAIN THE
 REQUIRED NEGATIVE PRESSURE IN THE ROOM AND THE REQUIRED
 AIR CHANGES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  