| Plan Review Notes For Permit 19040567 |
| Permit Number |
19040567 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-18 13:46:48 | | | | | | 2019-04-15 07:23:44 | 04/15/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THIS PRESSURE VACUUM BREAKER MODEL 800M4FR IS NOT A | | | LEAD-FREE DEVICE WHICH IS REQUIRED BY THE CITY OF WEST | | | PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR | | | CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB | | | .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA | | | CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE | | | INFORMATION. THE LF800M4QT MODEL IS A LEAD FREE DEVICE | | | SO PLEASE RESUBMIT SPECS FOR IT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|