| 2019-05-20 15:38:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040533 |
| | 5/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW |
| | ADDITION- SEE SECTIONS C502.1, C401.2 & C101.5.1 FBC |
| | EC. |
| | |
| | 2) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD |
| | AND EXHAUST SYSTEM HOWEVER AN AIR BALANCE CALCULATION |
| | SHALL BE PROVIDED ON THE MAIN PLANS- SECTION 508.1.2 |
| | FBC M. A) PLEASE NOTE THAT THE TEMPERATURE DIFFERENTIAL |
| | BETWEEN THE MAKEUP AIR AND THE AIR IN THE CONDITIONED |
| | SPACE SHALL NOT EXCEED 10 DEGEES F- SEE SECTION 508.1.1 |
| | AND VERIFY COMPLIANCE. |
| | |
| | 3) SHEET M0.1, IAQ VENTILATION DESIGN CRITERIA: NO |
| | INFORMATION HAS BEEN PROVIDED FOR AN ENGINEERED |
| | VENTILATION SYSTEM (SECTION 403.2) THEREFORE THE |
| | VENTILATION RATES SHALL BE IN ACCORDANCE WITH TABLE |
| | 403.3.1.1 FBC M. PLEASE CORRECT THE RATES FOR THE |
| | CLASSROOMS TO BE BASED ON 35 PERSONS PER 1000 SF. AT 10 |
| | CFMS PER OCCUPANT + 0.12 CFMS PER SF. A) PLEASE UPDATE |
| | THE 2014 REFERENCE IN THE NOTES UNDER THE TABLE TO |
| | 2017. |
| | |
| | 4) M0.1, M2.1 & M4.01: DUCT SMOKE DETECTORS SHALL BE |
| | INSTALLED IN THE SUPPLY SYSTEMS OF THE NEW AHU'S- |
| | SECTION 606.2.1 FBC M. CORRECT THE HVAC DESIGN TABLE |
| | AND PROVIDE SYMBOLS AT THE APPROPRIATE LOCATIONS ON THE |
| | PLAN AND ON THE CONTROLS DIAGRAMS. PLEASE PROVIDE A |
| | NARRATIVE TO CLARIFY THE CONTROLS OPERATION AND HOW THE |
| | DETECTORS WILL BE SUPERVISED- SECTIONS 606.4 AMND |
| | 606.4.1 FBC M. |
| | |
| | 5) M2.1: LABEL THE DIFFUSERS IN THE NEW ADDITIONS AND |
| | PROVIDE THE CFM SUPPLY AT EACH DROP- SECTION 603.1 FBC |
| | M. |
| | |
| | 6) M2.1 & M4.1: PROVIDE ENGINEERED DETAILS FOR |
| | INSTALLATION OF THE CONDENSERS AND MOUNTING PADS- |
| | SECTION 301.15 FBC M. |
| | |
| | 7) M21: CLARIFY IF ANY CHANGES WILL BE MADE TO THE |
| | RESTOROOM EXHAUST SYSTEMS AND PROVIDE DETAILS IF |
| | APPLICABLE- SECTION 107.2.1 FBC M. |
| | |
| | 8) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR |
| | HANDLERS- SECTION 307.2.1 FBC M. |
| | |
| | 9) SHEET K101 & M0.1: PROVIDE COMBUSTUION AIR |
| | CALCULATIONS FOR THE NEW GAS-FIRED COOKING APPLIANCES |
| | AND SHOW HOW THE AIR WILL BE PROVIDED- SECTION 304 FBC |
| | FG. A) SUBMIT CUT SHEETS FOR THE APPLIANCES- SECTION |
| | 623.1 FBC FG. |
| | |
| | 10) THE KITCHEN VENTILATION PLANS SHALL BE SIGNED AND |
| | SEALED BY THE DESIGN PROFESSIONAL OR BE MARKED "FOR |
| | REFERENCE ONLY" - SEE SECTION 107.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |