Plan Review Notes
Plan Review Notes For Permit 19040533
Permit Number 19040533
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-20 15:38:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040533
 5/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW
 ADDITION- SEE SECTIONS C502.1, C401.2 & C101.5.1 FBC
 EC.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD
 AND EXHAUST SYSTEM HOWEVER AN AIR BALANCE CALCULATION
 SHALL BE PROVIDED ON THE MAIN PLANS- SECTION 508.1.2
 FBC M. A) PLEASE NOTE THAT THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE SHALL NOT EXCEED 10 DEGEES F- SEE SECTION 508.1.1
 AND VERIFY COMPLIANCE.
  
 3) SHEET M0.1, IAQ VENTILATION DESIGN CRITERIA: NO
 INFORMATION HAS BEEN PROVIDED FOR AN ENGINEERED
 VENTILATION SYSTEM (SECTION 403.2) THEREFORE THE
 VENTILATION RATES SHALL BE IN ACCORDANCE WITH TABLE
 403.3.1.1 FBC M. PLEASE CORRECT THE RATES FOR THE
 CLASSROOMS TO BE BASED ON 35 PERSONS PER 1000 SF. AT 10
 CFMS PER OCCUPANT + 0.12 CFMS PER SF. A) PLEASE UPDATE
 THE 2014 REFERENCE IN THE NOTES UNDER THE TABLE TO
 2017.
  
 4) M0.1, M2.1 & M4.01: DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY SYSTEMS OF THE NEW AHU'S-
 SECTION 606.2.1 FBC M. CORRECT THE HVAC DESIGN TABLE
 AND PROVIDE SYMBOLS AT THE APPROPRIATE LOCATIONS ON THE
 PLAN AND ON THE CONTROLS DIAGRAMS. PLEASE PROVIDE A
 NARRATIVE TO CLARIFY THE CONTROLS OPERATION AND HOW THE
 DETECTORS WILL BE SUPERVISED- SECTIONS 606.4 AMND
 606.4.1 FBC M.
  
 5) M2.1: LABEL THE DIFFUSERS IN THE NEW ADDITIONS AND
 PROVIDE THE CFM SUPPLY AT EACH DROP- SECTION 603.1 FBC
 M.
  
 6) M2.1 & M4.1: PROVIDE ENGINEERED DETAILS FOR
 INSTALLATION OF THE CONDENSERS AND MOUNTING PADS-
 SECTION 301.15 FBC M.
  
 7) M21: CLARIFY IF ANY CHANGES WILL BE MADE TO THE
 RESTOROOM EXHAUST SYSTEMS AND PROVIDE DETAILS IF
 APPLICABLE- SECTION 107.2.1 FBC M.
  
 8) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS- SECTION 307.2.1 FBC M.
  
 9) SHEET K101 & M0.1: PROVIDE COMBUSTUION AIR
 CALCULATIONS FOR THE NEW GAS-FIRED COOKING APPLIANCES
 AND SHOW HOW THE AIR WILL BE PROVIDED- SECTION 304 FBC
 FG. A) SUBMIT CUT SHEETS FOR THE APPLIANCES- SECTION
 623.1 FBC FG.
  
 10) THE KITCHEN VENTILATION PLANS SHALL BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OR BE MARKED "FOR
 REFERENCE ONLY" - SEE SECTION 107.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE