| 2019-09-06 11:59:57 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | PREVIOUS COMMENT 2ND REQUEST 15) SUBMIT TWO COPIES OF | | | THE MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION | | | MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE | | | SEC. 402.2, AND 301.3.GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1. | | | | | | NEW COMMENT: | | | | | | 1) THE GAS PIPING FOR THE KITCHEN APPLIANCES IS | | | UNDERSIZED USING TABLE 402.4(2) AND THE LONGEST LENGTH | | | METHOD AT 80' THE FIRST SECTION SHALL BE 11/2" THE 2ND | | | AND 3RD SECTIONS SHALL BE 11/4" THE LAST SECTION IS 1". | | | PER FBC FG TABLE 402.4(2) AND 402.4.1 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|