Plan Review Notes
Plan Review Notes For Permit 19040533
Permit Number 19040533
Review Stop G
Sequence Number 1
Notes
Date Text
2019-09-06 11:59:572ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 PREVIOUS COMMENT 2ND REQUEST 15) SUBMIT TWO COPIES OF
 THE MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3.GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1.
  
 NEW COMMENT:
  
 1) THE GAS PIPING FOR THE KITCHEN APPLIANCES IS
 UNDERSIZED USING TABLE 402.4(2) AND THE LONGEST LENGTH
 METHOD AT 80' THE FIRST SECTION SHALL BE 11/2" THE 2ND
 AND 3RD SECTIONS SHALL BE 11/4" THE LAST SECTION IS 1".
 PER FBC FG TABLE 402.4(2) AND 402.4.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
  
  
  
  
  
  