| Plan Review Notes For Permit 19040533 |
| Permit Number |
19040533 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-20 14:10:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THE ARE INDICATIONS OF A HOOD SYSTEM IN THE KITCHEN. | | | | | | THE HOOD AND FIRE SUPRESSION SYSTEMS SHALL BE SUBMITTED | | | AND INSTALLED UNDER SEPRATE PERMITS AND SHOP DRAWING. | | | | | | THE APPROVAL OF THIS PERMIT IS ONLY CONCEPTUAL FOR THE | | | HOOD AND SUPPRESSION SYSTEM. | | | | | | PLEASE ENSURE THAT SHOP DRAWINGS ARE PROPOERLY | | | SUBMITTED. | | | | | | | | | | | | 2) THERE APPEARS TO BE AN EXISTING DOOR IN A 2 HOUR | | | FIRE RATED WALL AT THE EXISTING A/C ROOM THAT IS NOT | | | CLEARLY INDICATED IN THE DOOR SCHEDDULE AS HAVING THE | | | REQUIRED RATING. | | | | | | PLEASE ENSURE THIS DOES IS PROPERLY TAGGED/INDICATED | | | WITH THE APPLICABLE FIRE RATING FOR THIS WALL. | | | | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|