| Plan Review Notes For Permit 19040533 |
| Permit Number |
19040533 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-17 10:32:46 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E 3.2 | | | | | | 600A PANEL SHOWS MAIN LUG, AND MAIN BREAKER??? CAN'T BE | | | BOTH!!! | | | | | | FAULT CURRENT REQUIRED FOR SERVICE, 110.24 | | | | | | RISER SHOWS NO WIRE SIZES NEED TO SHOW WIRE SIZES FOR | | | ALL. | | | | | | LOAD CALCULATION FOR "T" NEED TO SHOW HOW LOAD WAS | | | CALCULATED PERCENTAGES USED NOT SHOWN IN CODE BOOK. |
|