| 2019-06-05 12:52:03 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19040533 |
| | REVIEWED: JUNE 5, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN |
| | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW |
| | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE |
| | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR |
| | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS |
| | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION |
| | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, |
| | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR |
| | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL |
| | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED |
| | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS |
| | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE |
| | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN |
| | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW |
| | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED |
| | DEVELOPMENTS. |
| | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. |
| | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES |
| | COORDINATOR 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 502.1 FBC[CE] GENERAL. ADDITIONS TO AN EXISTING |
| | BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE |
| | PROVISIONS RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING |
| | THE UNALTERED PORTION OF THE EXISTING BUILDING OR |
| | BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS |
| | SHALL NOT CREATE AN UNSAFE OR HAZARDOUS CONDITION OR |
| | OVERLOAD EXISTING BUILDING SYSTEMS. AN ADDITION SHALL |
| | BE DEEMED TO COMPLY WITH THIS CODE IF THE ADDITION |
| | ALONE COMPLIES OR IF THE EXISTING BUILDING AND ADDITION |
| | COMPLY WITH THIS CODE AS A SINGLE BUILDING. ADDITIONS |
| | SHALL COMPLY WITH SECTION C502.2. ADDITIONS COMPLYING |
| | WITH ANSI/ASHRAE/IESNA 90.1. NEED NOT COMPLY WITH |
| | SECTIONS C402, C403, C404 AND C405. |
| | - THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS ARE |
| | FOR HVAC ONLY. PROVIDE DOCUMENTATION OF COMPLIANCE FOR |
| | THE BUILDING ENVELOPE. |
| | |
| | 3) 506.3 FBC[B] FRONTAGE INCREASE. EVERY BUILDING SHALL |
| | ADJOIN OR HAVE ACCESS TO A PUBLIC WAY TO RECEIVE AN |
| | AREA FACTOR INCREASE BASED ON FRONTAGE. AREA FACTOR |
| | INCREASE SHALL BE DETERMINED IN ACCORDANCE WITH |
| | SECTIONS 506.3.1 THROUGH 506.3.3. |
| | - PROVIDE CALCULATION FOR AREA INCREASE. USING FRONTAGE |
| | ALONG BOTH STREETS WILL GET YOU ENOUGH INCREASE, BUT |
| | THE EQUATION NEEDS TO SHOW ON PLANS. |
| | |
| | 4A) 506.3 FBC[B] FRONTAGE INCREASE. |
| | - SHEET A0.0. PLEASE ADD THE PROPOSED ADDITION |
| | CONSTRUCTION TYPE AND ADD TOTAL AREA OF EXISTING AND |
| | PROPOSED ADDITION. TOTAL SHOULD BE 10573+1254=11827 |
| | |
| | 4B)506.3 FBC[B] FRONTAGE INCREASE. |
| | - ADD IF EITHER AREA SEPARATED BY FIRE WALL HAS |
| | SPRINKLERS, OR ENTER NON-SPRINKLED BLDG INTO DATA. |
| | |
| | 4C)506.3 FBC[B] FRONTAGE INCREASE. |
| | - PROVIDE THE AREA OF EACH SIDE OF THE EXISTING 2 HOUR |
| | FIRE WALL. |
| | |
| | 5) 602.1 FBC[B] GENERAL. BUILDINGS AND STRUCTURES |
| | ERECTED OR TO BE ERECTED, ALTERED OR EXTENDED IN HEIGHT |
| | OR AREA SHALL BE CLASSIFIED IN ONE OF THE FIVE |
| | CONSTRUCTION TYPES DEFINED IN SECTIONS 602.2 THROUGH |
| | 602.5. |
| | - SHOW 2 HR FIRE RESISTANCE RATING AT EXTERIOR WALLS AS |
| | REQUIRED FOR IIIB (SEE TABLE 601) . |
| | |
| | 6) SHEET A2.9. CHECK ELEVATION CALL OUTS ON ENLARGED |
| | RESTROOM. SOME CALLOUTS DO NOT MATCH THE ELEVATION |
| | NUMBER. |
| | - CALLOUT NUMBERS 1, 2, 3 AND 4. |
| | |
| | 7) SHEET A3.5 |
| | - DETAILS 2 AND 4 FOR MILLWORK. 2SHOWS 36 INCHES AT |
| | BASE CABINET AND 3 SHOWS 24 INCHES TOP OF COUNTER. |
| | PLEASE COORDINATE THE DETAILS TO MATCH COUNTERTOP |
| | HEIGHT. IT LOOKS LIKE DETAIL 2 USED 34 INCHES TO MEET |
| | FBC ACCESSIBILITY. |
| | |
| | 8) 903.2.11.5 FBC[R] COMMERCIAL COOKING OPERATIONS. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN |
| | COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEMS WHERE |
| | AN AUTOMATIC SPRINKLER SYSTEM IS USED TO COMPLY WITH |
| | SECTION 904. |
| | - SEPARATE PERMIT NEEDED FOR KITCHEN HOOD. |
| | |
| | 9) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| | - PLANS CALL FOR GEOTECHNICAL REPORT. PLEASE UPLOAD |
| | INTO SUPPORTING DOCUMENTS IN PROJECTDOX. |
| | |
| | 10) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING |
| | AS STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS |
| | #7. |
| | - PROVIDE ENGINEERING FOR ENHANCED NAILING AS REQUIRED |
| | IN NOA 18-0919.06. |
| | |
| | 11) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL AND |
| | ATTACHMENT FOR INSULATION AT ROOF DECK, OR INDICATE |
| | THAT HOW INSULATION IS INSTALLED AT ROOF. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |