2019-06-05 12:52:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19040533
 REVIEWED: JUNE 5, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 2) 502.1 FBC[CE] GENERAL. ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING
 THE UNALTERED PORTION OF THE EXISTING BUILDING OR
 BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS
 SHALL NOT CREATE AN UNSAFE OR HAZARDOUS CONDITION OR
 OVERLOAD EXISTING BUILDING SYSTEMS. AN ADDITION SHALL
 BE DEEMED TO COMPLY WITH THIS CODE IF THE ADDITION
 ALONE COMPLIES OR IF THE EXISTING BUILDING AND ADDITION
 COMPLY WITH THIS CODE AS A SINGLE BUILDING. ADDITIONS
 SHALL COMPLY WITH SECTION C502.2. ADDITIONS COMPLYING
 WITH ANSI/ASHRAE/IESNA 90.1. NEED NOT COMPLY WITH
 SECTIONS C402, C403, C404 AND C405.
 - THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS ARE
 FOR HVAC ONLY. PROVIDE DOCUMENTATION OF COMPLIANCE FOR
 THE BUILDING ENVELOPE.
  
 3) 506.3 FBC[B] FRONTAGE INCREASE. EVERY BUILDING SHALL
 ADJOIN OR HAVE ACCESS TO A PUBLIC WAY TO RECEIVE AN
 AREA FACTOR INCREASE BASED ON FRONTAGE. AREA FACTOR
 INCREASE SHALL BE DETERMINED IN ACCORDANCE WITH
 SECTIONS 506.3.1 THROUGH 506.3.3.
 - PROVIDE CALCULATION FOR AREA INCREASE. USING FRONTAGE
 ALONG BOTH STREETS WILL GET YOU ENOUGH INCREASE, BUT
 THE EQUATION NEEDS TO SHOW ON PLANS.
  
 4A) 506.3 FBC[B] FRONTAGE INCREASE.
 - SHEET A0.0. PLEASE ADD THE PROPOSED ADDITION
 CONSTRUCTION TYPE AND ADD TOTAL AREA OF EXISTING AND
 PROPOSED ADDITION. TOTAL SHOULD BE 10573+1254=11827
  
 4B)506.3 FBC[B] FRONTAGE INCREASE.
 - ADD IF EITHER AREA SEPARATED BY FIRE WALL HAS
 SPRINKLERS, OR ENTER NON-SPRINKLED BLDG INTO DATA.
  
 4C)506.3 FBC[B] FRONTAGE INCREASE.
 - PROVIDE THE AREA OF EACH SIDE OF THE EXISTING 2 HOUR
 FIRE WALL.
  
 5) 602.1 FBC[B] GENERAL. BUILDINGS AND STRUCTURES
 ERECTED OR TO BE ERECTED, ALTERED OR EXTENDED IN HEIGHT
 OR AREA SHALL BE CLASSIFIED IN ONE OF THE FIVE
 CONSTRUCTION TYPES DEFINED IN SECTIONS 602.2 THROUGH
 602.5.
 - SHOW 2 HR FIRE RESISTANCE RATING AT EXTERIOR WALLS AS
 REQUIRED FOR IIIB (SEE TABLE 601) .
  
 6) SHEET A2.9. CHECK ELEVATION CALL OUTS ON ENLARGED
 RESTROOM. SOME CALLOUTS DO NOT MATCH THE ELEVATION
 NUMBER.
 - CALLOUT NUMBERS 1, 2, 3 AND 4.
  
 7) SHEET A3.5
 - DETAILS 2 AND 4 FOR MILLWORK. 2SHOWS 36 INCHES AT
 BASE CABINET AND 3 SHOWS 24 INCHES TOP OF COUNTER.
 PLEASE COORDINATE THE DETAILS TO MATCH COUNTERTOP
 HEIGHT. IT LOOKS LIKE DETAIL 2 USED 34 INCHES TO MEET
 FBC ACCESSIBILITY.
  
 8) 903.2.11.5 FBC[R] COMMERCIAL COOKING OPERATIONS. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEMS WHERE
 AN AUTOMATIC SPRINKLER SYSTEM IS USED TO COMPLY WITH
 SECTION 904.
 - SEPARATE PERMIT NEEDED FOR KITCHEN HOOD.
  
 9) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 - PLANS CALL FOR GEOTECHNICAL REPORT. PLEASE UPLOAD
 INTO SUPPORTING DOCUMENTS IN PROJECTDOX.
  
 10) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING
 AS STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 - PROVIDE ENGINEERING FOR ENHANCED NAILING AS REQUIRED
 IN NOA 18-0919.06.
  
 11) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL AND
 ATTACHMENT FOR INSULATION AT ROOF DECK, OR INDICATE
 THAT HOW INSULATION IS INSTALLED AT ROOF.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  