| Plan Review Notes For Permit 19040527 |
| Permit Number |
19040527 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-07 18:23:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | SUBMITTAL IS DENIED BY BUILDING. | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE VULT WINDSPEED ON THE APPROVED PLANS IS 170 MPH | | | AND ON SHEET 1 OF THE DOOR AND WINDOW ENGINEERING IT IS | | | SPECIFIED AS 165 MPH. PLEASE COORDINATE THE TWO. FBC | | | 107.2.1 | | | | | | 2) THE MAXIMUM DESIGN LOAD PRESSURES FOR WALL ZONES 4 | | | AND 5 ON SHEET 1 OF THE DOOR AND WINDOW ENGINEERING IS | | | LOWER THAN THE ONES SPECIFIED ON THE APPROVED PLANS. | | | PLEASE COORDINATE THE TWO. FBC 107.2.1 | | | THE PLANS HAVE +35.2 PSF, -38.2 PSF FOR ZONE 4 AND | | | +35.2 PSF, -47.0 PSF FOR ZONE 5. | | | | | | 3) WHEN BEING SUBMITTED FOR PUBLIC RECORD, THE 10 | | | SHEETS OF DOOR AND WINDOW DRAWINGS FROM THE ENGINEER, | | | THOMAS J. TWOMEY, P.E. ARE REQUIRED TO HAVE THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IN | | | ACCORDANCE WITH FAC 61G15-23.003 AND FS 471. | | | |
|