 SUBMITTAL IS DENIED BY BUILDING.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VULT WINDSPEED ON THE APPROVED PLANS IS 170 MPH
 AND ON SHEET 1 OF THE DOOR AND WINDOW ENGINEERING IT IS
 SPECIFIED AS 165 MPH. PLEASE COORDINATE THE TWO. FBC
 107.2.1
  
 2) THE MAXIMUM DESIGN LOAD PRESSURES FOR WALL ZONES 4
 AND 5 ON SHEET 1 OF THE DOOR AND WINDOW ENGINEERING IS
 LOWER THAN THE ONES SPECIFIED ON THE APPROVED PLANS.
 PLEASE COORDINATE THE TWO. FBC 107.2.1
 THE PLANS HAVE +35.2 PSF, -38.2 PSF FOR ZONE 4 AND
 +35.2 PSF, -47.0 PSF FOR ZONE 5.
  
 3) WHEN BEING SUBMITTED FOR PUBLIC RECORD, THE 10
 SHEETS OF DOOR AND WINDOW DRAWINGS FROM THE ENGINEER,
 THOMAS J. TWOMEY, P.E. ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IN
 ACCORDANCE WITH FAC 61G15-23.003 AND FS 471.
  