Plan Review Notes
Plan Review Notes For Permit 19040513
Permit Number 19040513
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-16 08:36:571) THE CLEAR FLOOR SPACE FOR THE HANDICAP ACCESSIBLE
 FIXTURES IN THE TOILET ROOMS IS CONFUSING. CLEARLY SHOW
 THE CLEAR FLOOR SPACES FOR THE WATER CLOSET AND THE
 LAVATORY ON THE PLANS. SHOW THE LENGTH AND WIDTH
 DIMENSIONS OF EACH CLEAR FLOOR SPACE ON THE PLANS.
 COMPLY WITH 2017 FBC-ACCESS. SECS.305, 306, 604.3.1 &
 606.2.
 2) A CLEAR FLOOR SPACE SHALL BE PROVIDED AT THE BREAK
 ROOM SINK.SHOW THIS ON THE PLAN ALONG WITH THE
 DIMENSIONS. 2017 FBC-ACCESS. SEC.606.2.
 3) THE DOORS IN TOILET ROOMS # 107 & # 108 APPEAR TO
 SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORIES.
 COMPLY WITH 2017 FBC-ACCESS. SEC. 603.2.3. (SEE
 EXCEPTIONS).
 4) SHT. A-501 - ELEVATION #9 - SHOW THE LEADING EDGES
 OF THE DRINKING FOUNTAINS FROM THE FINISH FLOOR ON THE
 PLAN. PROTRUSION LIMITS SHALL COMPLY WITH 2017
 FBC-ACCESS. SEC.307.
 5) SHT. A-501 - ELEV. #9 - THE DRINKING FOUNTAINS SHALL
 BE PROVIDED WITH KNEE AND TOE CLEARANCES IN ACCCORDANCE
 WITH 2017 FBC- ACCESS. SEC. 306.
 6) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 WATER CLOSET FROM THE FINISH FLOOR TO THE TOP OF THE
 SEAT ON THE PLAN. COMPLY WITH 2017 FBC-ACCESS.
 SEC.604.4.
 7) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 GRAB BARS FROM THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE. 2017 FBC- SEC. 609.4.
 8) SHT. A-501 - ELEVS. #4 & #5 - THE LOCATION OF THE
 REAR AND SIDE GRAB BARS FOR THE WATER CLOSET SHALL
 COMPLY WITH 2017 FBC-ACCESS. SEC.604.5.1 & 604.5.2.
 SHOW THESE DIMENSIONS ON THE PLANS.
 9) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 LAVATORY FROM THE FINISH FLOOR TO THE TOP OF THE
 LAVATORY RIM. COMPLY WITH 2017 FBC-ACCESS. SEC.606.3.
 10) SHT. A-501 - ELEVS.#4 & #5 - SHOW THE KNEE AND TOE
 CLEARANCES FOR THE LAVATORIES ON THE PLANS. COMPLY WITH
 2017 FBC-ACCESS. SEC.606.2.
 11) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF
 THE TOILET PAPER DISPENSERS ABOVE THE FINISH FLOOR.
 COMPLY WITH 2017 FBC-ACCESS. SEC.604.7.
 12) SHT. A-501 - ELEVS. #3 & #5 - THE MAXIMUM HEIGHT OF
 THE CABINET IN THE TOILET ROOMS SHALL COMPLY WITH 2017
 FBC- ACCESS. SEC.308.2, 308.3.
 13) TEMPERD WATER IS REQUIRED AT THE LAVATORIES IN THE
 TOILET ROOMS PER 2017 FBC-PLUMBING SEC. 416.5.
 14) AN INLINE BACKFLOW PREVENTION DEVICE IS REQUIRED ON
 THE WATER SUPPLY TO THE COFFEEMAKER AND ALSO TO THE
 REFRIGERATOR. 2017 FBC-PLUMBING SEC. 608.3, 608.16.10.
 15) SHT. P-100 - THE FLOOR DRAINS ON THE SANITARY RISER
 ARE NOT PROPERLY VENTED. 2017 FBC-PLUMBING SEV.901.2.
 16) SHT. P-100 - THE INSTALLATION OF BACK TO BACK WATER
 CLOSETS SHALL COMPLY WITH 2017 FBC-PLUMBING SEC.706.3
 (EXCEPTION).
 17) THE HOT WATER PIPING AND RECIRCULATION WATER LINE
 SHALL BE INSULATED IN ITS ENTIRETY PER 2017 FBC-ENERGY
 SEC. C404.4. THE INSULATION THICKNESS SHALL BE IN
 ACCORDANCE WITH THE 2017 FBC-ENERGY TABLE C403.2.10.
 18) SUBMIT DETAILS AS TO THE DRAINAGE AND DISCHARGE OF
 RAINWATER FROM THE RROOF OF THIS STRUCTURE. WPB AMEND.
 TO FBC SEC. 1107.2.1, 2017 FBC-PLUMBING SEC.1101.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  