Plan Review Notes
Plan Review Notes For Permit 19040513
Permit Number 19040513
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-22 14:15:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET T 001 - UNDER CODE SUMMARY THE IS AN
 INDICATION OF N/A NEXT TO THE SPRINKLERED.
  
 THERE IS A FIRE SPRINKLER PLAN SHEET ATTACHED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET T 001 - UNDER CODE SUMMARY THERE IS AN
 INDICATION OF NFPA 72, 2010.
  
 THE CURRENT EDITION YEAR IS 2013.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT.
  
  
  
 3) SHEET T 001 - UNDER PROJECT SUMMARY THERE IS
 INDICATION STATING LIFE SAFETY SYTEMS OF FIRE
 EXTINGUISHER AND SMOKE DETECTORS.
  
 THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM NOR
 FIRE SPRINKLER ALARM.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 4) ELECTRICAL SHEETS - THERE ARE INDICATIONS OF FIRE
 ALARM DEVICES/EQUIPMENT BY NO INDICATION THAT ALL FIRE
 ALARM DEVICES/EQUIPMENT SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  