Plan Review Notes
Plan Review Notes For Permit 19040513
Permit Number 19040513
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-07 13:11:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040513
 ADD: 1831 PALM BEACH LAKES BLVD. SUITE:
 CONT: CLARO DEVELOPMENT
 TEL: 305-890-6192
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 07/ 2019
 ACTION: DENIED
  
 1) ALL OF THE ARCHITECTURAL SHEETS BY SCOTT P. WRASMAN
 ARE NOT SIGNED AND SEALED ELECTRONICALLY. ARCHITECTS:
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 2) THE STRUCTURAL SHEET BY NICHOLAS ANTHONY CAPOZZI P E
 ARE NOT SIGNED AND SEALED ELECTRONICALLY.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3A) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY LIST THE CONSTRUCTION TYPE AS TYPE VB. PLEASE
 NOTE THE SHELL BUILDING PERMIT FOR THIS BUILDING IS A
 CONSTRUCTION TYPE II-B (PERMIT 18101337). PLEASE UPDATE
 THE PLANS.
  
 3B) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY FIRE RESISTANCE/ BUILDING STRUCTURE LIST THE
 CONSTRUCTION TYPE AS TYPE VB. PLEASE NOTE THE SHELL
 BUILDING PERMIT FOR THIS BUILDING IS A CONSTRUCTION
 TYPE II-B (PERMIT 18101337). PLEASE UPDATE THE PLANS.
  
 3C) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY THE PLANS INDICATE SPRINKLERED N/A. PLEASE
 UPDATE PLANS, THE SHELL PERMIT (18101337) LIST FIRE
 SPRINKLERS AS PART OF THE PROJECT. TO DATE THERE IS AN
 ISSUED UNDERGROUND 6 INCH FIRE LINE (19030580) BEING
 INTRODUCED INTO THE PROJECT. UPDATE PLANS.
  
 3D) SHEET 001-T-001 THE COVER SHEET UNDER THE HEADING
 PROJECT SUMMARY LIST THIS STRUCTURE AS VB CONSTRUCTION
 TYPE WITH THE STRUCTURE CONSISTING OF A FRAMED ROOF
 WITH PLYWOOD DECK, TJI WOOD JOIST AND PARALAM BEAMS.
 THE PERIMETER WALLS ARE LOAD BEARING STRUCTURAL GAUGE
 STEEL STUDS.
 PLEASE UPDATE PLANS, UNDER THE SHELL PERMIT THE ROOF
 FRAMING SYSTEM, IS BAR JOIST WITH METAL B DECK. THE
 EXTERIOR BEARING WALLS ARE STRUCTURAL STEEL POST AND
 STEEL BEAM CONSTRUCTION WITH STRUCTURAL GAUGE STEEL
 INFILL WALLS, SEE SHELL PERMIT 18101337.
  
 4) THE SHEET 004-G-003 LIFE SAFETY AND ACCESSIBILITY
 SHEET INDICATE THAT THIS BUILDING IS TO CONFORM TO THE
 ANSI 1117.1 2009. PLEASE NOTE THE SUBMITTED PLANS WILL
 NEED TO CONFORM TO THE REQUIREMENTS OF THE 2017
 FBC-ACCESSIBILITY CODE. THIS CODE IS ADOPTED AS PART OF
 THE FLORIDA BUILDING CODE BY LAW, S.553.73(1)(A),
 FLORIDA STATUTES. THE ADMINISTRATIVE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING, CHAPTER 1.
  
 5) SHEET 015-A-501 SHOWS ELEVATIONS 3, 4 & 5 WITH NO
 DIMENSIONS (ELEVATION) TO THE GRAB BARS FOR THE WATER
 CLOSET. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107
 & 108 WITH THE BOTTOM OF THE MIRROR BOTTOM OF MIRROR AT
 3 FEET 4 INCHES. PLEASE REVIEW 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107
 & 108 WITH THE BOTTOM OF THE CABINET FURN529 AT 4 FEET
 6 INCHES FROM THE FLOOR. THESE CABINETS ARE AMOUNTED
 ABOVE THE REACH RANGES.
 2017 FBC-ACCESSIBILITY CODE, 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 8A) SHEET M-100 ROOF TOP EQUIPMENT SHOWS WITH NOTE 3 A
 NEW ROOFTOP CONDENSER HP-1 TO BE MOUNTED ON ROOF RACKS
 SEE M-200. M-200 THE CONDENSING UNIT STAND. THE DETAIL
 INDICATES THE USE OF A FLORIDA APPROVAL FL # 24546.1
 SUBMIT THE APPROVAL PLEASE.
 PLEASE SHOW COMPLIANCE WITH 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS.
  
 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8C) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 8D) WITHIN THE ROOF TOP CONDENSING STAND DETAIL THERE
 IS A STATEMENT THE CONTRACTOR TO VERIFY THE THICKNESS
 OF THE ROOF ASSEMBLY 18 INCHES CLEARANCE REQUIRED FROM
 THE BOTTOM OF THE SUPPORT RACK HORIZONTAL STRUCTURAL
 MEMBER TO THE TOP OF THE ROOF ASSEMBLY. PLEASE NOTE THE
 VERTICAL CLEAR MEASUREMENT DEPENDS ON THE WIDTH OF THE
 MECHANICAL UNIT (IN INCHES) PLEASE REVIEW THE 2017
 FBC-B TABLE 1510.10, CLEARANCE BELOW RAISED ROOF
 MOUNTED MECHANICAL UNITS.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER