| 2019-05-07 13:11:42 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040513 |
| | ADD: 1831 PALM BEACH LAKES BLVD. SUITE: |
| | CONT: CLARO DEVELOPMENT |
| | TEL: 305-890-6192 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 07/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) ALL OF THE ARCHITECTURAL SHEETS BY SCOTT P. WRASMAN |
| | ARE NOT SIGNED AND SEALED ELECTRONICALLY. ARCHITECTS: |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR |
| | DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY |
| | TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | 2) THE STRUCTURAL SHEET BY NICHOLAS ANTHONY CAPOZZI P E |
| | ARE NOT SIGNED AND SEALED ELECTRONICALLY. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3A) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE |
| | SUMMARY LIST THE CONSTRUCTION TYPE AS TYPE VB. PLEASE |
| | NOTE THE SHELL BUILDING PERMIT FOR THIS BUILDING IS A |
| | CONSTRUCTION TYPE II-B (PERMIT 18101337). PLEASE UPDATE |
| | THE PLANS. |
| | |
| | 3B) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE |
| | SUMMARY FIRE RESISTANCE/ BUILDING STRUCTURE LIST THE |
| | CONSTRUCTION TYPE AS TYPE VB. PLEASE NOTE THE SHELL |
| | BUILDING PERMIT FOR THIS BUILDING IS A CONSTRUCTION |
| | TYPE II-B (PERMIT 18101337). PLEASE UPDATE THE PLANS. |
| | |
| | 3C) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE |
| | SUMMARY THE PLANS INDICATE SPRINKLERED N/A. PLEASE |
| | UPDATE PLANS, THE SHELL PERMIT (18101337) LIST FIRE |
| | SPRINKLERS AS PART OF THE PROJECT. TO DATE THERE IS AN |
| | ISSUED UNDERGROUND 6 INCH FIRE LINE (19030580) BEING |
| | INTRODUCED INTO THE PROJECT. UPDATE PLANS. |
| | |
| | 3D) SHEET 001-T-001 THE COVER SHEET UNDER THE HEADING |
| | PROJECT SUMMARY LIST THIS STRUCTURE AS VB CONSTRUCTION |
| | TYPE WITH THE STRUCTURE CONSISTING OF A FRAMED ROOF |
| | WITH PLYWOOD DECK, TJI WOOD JOIST AND PARALAM BEAMS. |
| | THE PERIMETER WALLS ARE LOAD BEARING STRUCTURAL GAUGE |
| | STEEL STUDS. |
| | PLEASE UPDATE PLANS, UNDER THE SHELL PERMIT THE ROOF |
| | FRAMING SYSTEM, IS BAR JOIST WITH METAL B DECK. THE |
| | EXTERIOR BEARING WALLS ARE STRUCTURAL STEEL POST AND |
| | STEEL BEAM CONSTRUCTION WITH STRUCTURAL GAUGE STEEL |
| | INFILL WALLS, SEE SHELL PERMIT 18101337. |
| | |
| | 4) THE SHEET 004-G-003 LIFE SAFETY AND ACCESSIBILITY |
| | SHEET INDICATE THAT THIS BUILDING IS TO CONFORM TO THE |
| | ANSI 1117.1 2009. PLEASE NOTE THE SUBMITTED PLANS WILL |
| | NEED TO CONFORM TO THE REQUIREMENTS OF THE 2017 |
| | FBC-ACCESSIBILITY CODE. THIS CODE IS ADOPTED AS PART OF |
| | THE FLORIDA BUILDING CODE BY LAW, S.553.73(1)(A), |
| | FLORIDA STATUTES. THE ADMINISTRATIVE REQUIREMENTS OF |
| | THE FLORIDA BUILDING CODE, BUILDING, CHAPTER 1. |
| | |
| | 5) SHEET 015-A-501 SHOWS ELEVATIONS 3, 4 & 5 WITH NO |
| | DIMENSIONS (ELEVATION) TO THE GRAB BARS FOR THE WATER |
| | CLOSET. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 |
| | POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN |
| | A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 6) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107 |
| | & 108 WITH THE BOTTOM OF THE MIRROR BOTTOM OF MIRROR AT |
| | 3 FEET 4 INCHES. PLEASE REVIEW 603.3 MIRRORS. 2017 |
| | FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107 |
| | & 108 WITH THE BOTTOM OF THE CABINET FURN529 AT 4 FEET |
| | 6 INCHES FROM THE FLOOR. THESE CABINETS ARE AMOUNTED |
| | ABOVE THE REACH RANGES. |
| | 2017 FBC-ACCESSIBILITY CODE, 308 REACH RANGES |
| | 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| | OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 8A) SHEET M-100 ROOF TOP EQUIPMENT SHOWS WITH NOTE 3 A |
| | NEW ROOFTOP CONDENSER HP-1 TO BE MOUNTED ON ROOF RACKS |
| | SEE M-200. M-200 THE CONDENSING UNIT STAND. THE DETAIL |
| | INDICATES THE USE OF A FLORIDA APPROVAL FL # 24546.1 |
| | SUBMIT THE APPROVAL PLEASE. |
| | PLEASE SHOW COMPLIANCE WITH 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (G) PRE-ENGINEERED A/C STANDS. |
| | |
| | 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8C) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 8D) WITHIN THE ROOF TOP CONDENSING STAND DETAIL THERE |
| | IS A STATEMENT THE CONTRACTOR TO VERIFY THE THICKNESS |
| | OF THE ROOF ASSEMBLY 18 INCHES CLEARANCE REQUIRED FROM |
| | THE BOTTOM OF THE SUPPORT RACK HORIZONTAL STRUCTURAL |
| | MEMBER TO THE TOP OF THE ROOF ASSEMBLY. PLEASE NOTE THE |
| | VERTICAL CLEAR MEASUREMENT DEPENDS ON THE WIDTH OF THE |
| | MECHANICAL UNIT (IN INCHES) PLEASE REVIEW THE 2017 |
| | FBC-B TABLE 1510.10, CLEARANCE BELOW RAISED ROOF |
| | MOUNTED MECHANICAL UNITS. |
| | |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |