| 2019-05-14 15:02:55 | MECHANICAL PLAN REVIEW FAIL |
| | |
| | 1- NEED EQUIPMENT SIZING PER 2017 - FLORIDA BUILDING |
| | CODE - ENERGY CONSERVATION SEC R403.7.1 EQUIPMENT |
| | SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT |
| | SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE |
| | LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING |
| | EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR |
| | GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR |
| | THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS |
| | INSTALLED. |
| | |
| | 2 NEED ENERGY PERFORMANCE LEVEL PER 2017 - FLORIDA |
| | BUILDING CODE - ENERGY CONSERVATION SEC R401.3 ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD (MANDATORY) THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND |
| | CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT |
| | BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. |
| | FLORIDA LAW (SECTION 553.9085, FLORIDA STATUTES) |
| | REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN |
| | ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND |
| | NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD |
| | CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE |
| | LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A |
| | DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT |
| | THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE |
| | BUILDER ACCURATELY REFLECTS THE PLANS AND |
| | SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE |
| | FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE |
| | FOUND IN APPENDIX RD. |
| | |
| | CHRIS MONTELLO |
| | 805-6733 |
| | |
| | |
| | |