| 2019-05-03 09:16:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. THERE |
| | ARE NOTES IN 2 LOCATIONS THAT CONFLICT WITH CODE, NOTE |
| | 13 IN ELECTRICAL NOTES AND THE FIRST NOTE SHOWN UNDER |
| | "FOR NEW ELECTRIC ONLY". ALL BRANCH CIRCUITS THAT |
| | SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 3. PANEL SCHEDULE STATES THAT PANEL A IS EXISTING, BUT |
| | THE RISER DIAGRAM STATES THAT IT IS A NEW PANEL. |
| | CORRECT DISCREPANCY. WPB FBC 107.2.1 |
| | 4. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 7. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| | SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 9. TWO NOTES STATE THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. ONE OF THE NOTES |
| | CITES THE 2008 NEC WHICH IS NOT THE CURRENT CODE. |
| | PROVIDE CORRECTION. ELECTRICAL NOTE 14 AND SECOND NOTE |
| | UNDER "FOR NEW ELECTRIC ONLY". NEC 406.12; FBC RE |
| | E4002.14; FBC PREFACE |
| | 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LOAD CALULATION PROVIDED DOES NOT INCLUDE THE |
| | SQUARE FOOTAGE DEMAND AS PER THE FBC RESIDENTIAL |
| | METHOD. NEC 220; FBC RE E3602.2 |
| | 11. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | 12. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| | FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| | IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| | NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| | NEC 210.52(C)(1); FBC RE E3901 |
| | 13. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | PROVIDE CORRECTION FOR BATH 1. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE E3703.4, E3901.6 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |