2019-05-17 14:32:56NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2-PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2 AND
 R101.5 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE SURVEY (2 COPIES) SHOWING ALL THE
 INFORMATION REQUIRED BY SEC. 107.2.5 CITY AMENDMENTS.
  
 4- WINDOWS ON BEDROOMS #1 AND #2 DON'T COMPLY WITH THE
 EGRESS REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
 NOTE: ARCHITECT TO SPECIFY TYPE OF WINDOW ON THE WINDOW
 SCHEDULE. . COORDINATE WITH PRODUCT APPROVAL. BASED ON
 SINGLE HUNG WINDOW PRODUCT APPROVAL SUBMITTED, WINDOW
 TYPE "A" DOESN'T COMPLY WITH EGRESS. REVISE AS
 REQUIRED.
 ALSO, SIZE OF WINDOWS SHOWN ON THE WINDOW SCHEDULE ARE
 INCORRECT. FOR EXAMPLE, ACCORDING TO EXTERIOR
 ELEVATIONS, WINDOW "F" ARE TWO WINDOWS MULLED TOGETHER
 NOT JUST ONE WINDOW SIZE 72"X60". REVISE AS REQUIRED.
 PLEASE COORDINATE WINDOW SCHEDULE WITH ALL WINDOWS
 SHOWN ON PLANS AND ELEVATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ENTRY DOOR AND SIDE WINDOW AS SHOWN ON PLANS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R101301.1 FBC-RESIDENTIAL.
  
 6- THERE IS A NEW ROOF FOR THE ENTIRE HOUSE:
 A)ARCHITECT TO SPECIFY ALL THE DEAD AND LIVE LOADS,
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL (NOTE: TAKE INTO CONSIDERATION
 FOOTNOTES "B" AND "G" OF TABLE R301.5 TO AVOID
 CONFLICTS/DELAYS).
  
 B) ARCHITECT TO SPECIFY ATTIC ACCESS SIZE AND LOCATION.
 SEC. R307.1 FBC-RESIDENTIAL.
  
 7- REVISE THE ROOF EDGE ZONE DISTANCE SPECIFIED ON THE
 DESIGN WIND PRESSURES ON SHEET CVR.
 THE MINIMUM DISTANCE FOR EDGE AND CORNER AREAS IS 4
 FEET NOT 3 FEET AS REQUIRED BY NOTE "A" ON FIGURE
 R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 8- CLARIFY/REVISE FLOOD ZONE INFORMATION SHOWN ON SHEET
 SP-1.
 PER SEC. 18-284 CITY ORDINANCE NO. 4729-17 NEW FLOOD
 INSURANCE RATE MAPS WERE ADOPTED ON OCTOBER 5, 2017.
 THERE ARE NO MORE FLOOD ZONES "B". ALSO, NOTES SHOWN
 UNDER THE FLOOD ZONE INFORMATION DON'T CORRESPOND TO
 THE CITY OF WEST PALM BEACH. REVISE AS REQUIRED.
 NOTE: THIS PROPERTY IS NOT LOCATED IN A FLOOD HAZARD
 AREA.
  
 9- SHEET SP-2: AREAS SHOWN ON THE AREA CALCULATIONS AND
 PROPOSED SITE PLAN DON'T MATCH. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- REVISE THE FOOTING MINIMUM DEPTH SHOWN ON THE WALL
 SECTION ON SHEET A-1. NEED 12" MIN. DEPTH. SEC.
 R403.1.4 FBC-RESIDENTIAL. ALSO, VERTICAL REINFORCEMENT
 NOTE ON SAME WALL IS REFERENCING THE SFBC. THIS CODE NO
 LONGER EXISTS. REVISE AS REQUIRED.
  
 11- WOOD INFILL DETAIL 4/A-3: CLARIFY CONNECTOR
 SPECIFIED TO FASTEN THE WOOD STUDS. WHAT IS "SIMPSON
 UPC". SEC. R301.1 FBC-RESIDENTIAL.
  
 12- SHEET A-4:
 A)FOOTING F3 SHOWN ON THE FOOTING SCHEDULE DOESN'T
 MATCH FOOTING SHOWN ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) SPECIFICATIONS SHOWN ON THE FOUNDATION PLAN AND
 DETAILS PROVIDED ARE NOT CLEAR. THEY NEED TO BE
 COORDINATED. DETAIL 2/A-4 IS FOR FOOTINGS OR FOR TIE
 BEAMS?. IF THIS DETAIL IS FOR FOOTING, THEN CLARIFY HOW
 IS THE PROPOSED 3" CONCRETE SLAB GOING TO HAVE 2 #5
 TIES THE WAY IS SHOWN ON THIS DETAIL. NOTE: CONSIDER
 THE REQUIRED REINFORCEMENT CLEARANCE. THE SEC. 107.2.1
 CITY AMENDMENTS.
  
 C)CLARIFY GENERAL CONSTRUCTION NOTE SHOWN AT THE BOTTOM
 OF SHEET. THERE IS NOT POOL IN THIS PROJECT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY THICKNESS OF VAPOR BARRIER. FOUNDATION PLAN
 NOTES AND TYPICAL CONCRETE COL. TO FOOTING DETAIL ON
 SAME SHEET DON'T MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 13-SHEET A-5:
 A)ROOF FRAMING PLAN SHOWS A NEW 4"X12" STEEL I BEAM BY
 THE NEW KITCHEN AREA. THERE ARE NO DETAILS AND
 SPECIFICATIONS ON THE FOUNDATION PLAN FOR COLUMNS AND
 FOOTING TO SUPPORT THIS BEAM. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS. ALSO, SPECIFY CONNECTIONS AT THE
 ENDS OF THIS BEAM. ALSO, PROVIDE DETAILS AND
 SPECIFICATION FOR FASTENING OF ROOF TRUSSES TO THIS
 BEAM. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE DETAILS AND SPECIFICATIONS FOR CONNECTIONS
 AT THE END OF ALL WOOD BEAMS SHOWN ON THE ROOF FRAMING
 PLAN. SEC. R301.1 FBC-RESIDENTIAL.
  
 C)SIZE OF PRECAST LINTEL SHOWN ON THE LINTEL SCHEDULE
 DON'T SEEM TO BE CORRECT. IT LOOKS LIKE SIZE OF
 OPENINGS ARE WIDER THAN SIZE OF LINTELS SPECIFIED.
 REVISE AS REQUIRED. AND, PROVIDE DETAIL AND
 SPECIFICATIONS SHOWN HOW ARE THE LINTELS SUPPORTED ON
 THE COLUMNS. SPECIFY HOW MUCH BEARING SUPPORT IS
 REQUIRED ON EACH END. SEC. R301.1 FBC-RESIDENTIAL.
  
 D) ROOF TRUSS CONNECTORS SPECIFIED ARE NOT CLEAR.
 CONNECTORS SPECIFIED ON THE TRUSS ANCHORAGE WOOD TO CMU
 SCHEDULE AND CONNECTORS SPECIFIED ON THE TRUSS ANCHOR
 SCHEDULE ON SAME SHEET DON'T MATCH. REVISE AS REQUIRED
 TO MATCH. ALSO, SIMPSON HETA 12 CONNECTORS DON'T
 PROVIDE AN UPLIFT VALUE OF 1810# AS SPECIFIED ON THE
 TRUSS ANCHORAGE WOOD TO CMU SCHEDULE. SEE SIMPSON
 CATALOG AND REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 E) THERE ARE NOTES NEXT TO THE ROOF FRAMING PLAN THAT
 DON'T APPLY TO THIS HOUSE. SEE REVISE AS REQUIRED TO
 AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) THERE MANY DIFFERENT SPECIFICATIONS ON THE SAME
 SHEET FOR THE NAIL TYPE AN SPACING OF THE ROOF
 SHEATHING. REVISE AS REQUIRED TO MATCH. NOTE: SEC.
 R803.2.3.1 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS
 MIN. THERE IS A NOTE UNDER THE PLYWOOD SHEATHING
 NAILING SCHEDULE STATING THAT "RING SHANK NOT REQ'D
 WHEN MEAN ROOF HT<25'. THIS IS INCORRECT. REVISE AS
 REQUIRED ALSO.
  
 14-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 15- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $129,486. THE
 PERMIT FEE BALANCE IS $2854.42.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  