| 2019-07-02 14:56:47 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1 RECEPTACLE NEEDS TO BE INSTALLED AT FRONT OF |
| | BUILDING |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE |
| | FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT |
| | ACCESS TO GRADE LEVEL. BALCONIES, DECKS, AND PORCHES |
| | THAT ARE ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT |
| | SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, |
| | OR PORCH SURFACE. |
| | |
| | KITCHEN COUNTER LOOKS TO BE MISSING OUTLETS FOR SPACING |
| | E3901.4 COUNTERTOP RECEPTACLES. |
| | IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTIONS E3901.4.1 THROUGH E3901.4.5 |
| | |
| | OUTLETS INSTALLED SHALL MEET E3902 OF FBC FOR GFCI AND |
| | AFCI PROTECTION. |
| | |
| | R315.1CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN |
| | ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT |
| | THAT EMITS CARBON MONOXIDE AS BYPRODUCT OF COMBUSTION |
| | SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM |
| | INSTALLED WITHIN |
| | 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. |