| 2019-06-26 13:08:58 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| | ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| | IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE). |
| | SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| | SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| | NOTE: THERE IS NO MUCH ROOM ON THE REAR OF THE LOT. |
| | CLEARLY SHOW HOW RETAINING THE WATER IN THE REAR OF THE |
| | LOT WITHOUT DUMPING INTO THE NEIGHBOR'S PROPERTY. |
| | |
| | RESPONSE: |
| | SURVEY WAS REVISED. BUT IT DOESN'T PROVIDE |
| | SPECIFICATIONS OF HOW TO KEEP THE WATER WITHIN THIS |
| | LOT. BASED ON THE GRADE ELEVATION SHOWN, IT LOOKS LIKE |
| | THE INTENTION IS TO CREATE A BERM ON THE REAR OF THE |
| | PROPERTY. THIS IS NOT ACCEPTABLE. NEED TO KEEP THE |
| | WATER WITHIN THE LOT. A BERM WILL DIRECT WATER TO THE |
| | ADJACENT PROPERTIES. NEED TO KEEP THE WATER WITHIN THE |
| | SITE. REVISE AS REQUIRED. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) OK. |
| | |
| | B)OK. |
| | |
| | ORIGINAL COMMENT: |
| | C) PROVIDE THE NAME OF THE PERSON DOING THE |
| | CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NAME OF PERSON DOING THE CALCULATIONS |
| | WAS NOT PROVIDED. |
| | |
| | ORIGINAL COMMENT: |
| | D) ACCORDING TO PROJECT INFORMATION ON TOP OF PAGE 2 OF |
| | 4, THE HOUSE WAS ROTATED 180 DEGREES. CLARIFY WHY ITEM |
| | #5 ON PAGE 1 OF 4 STATES THAT THIS IS NOT A WORST CASE |
| | SCENARIO AND THEN THE HOUSE IS ROTATED 180 DEGREES?. |
| | CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION |
| | OF THE HOUSE AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. REVISE CALCULATIONS AS REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT |
| | REVISED. |
| | |
| | ORIGINAL COMMENT: |
| | E)WINDOW AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| | INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO |
| | MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT |
| | REVISED. |
| | |
| | ORIGINAL COMMENT: |
| | F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT |
| | REVISED. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |