| 2019-05-16 18:18:44 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE). |
| | SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| | SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| | NOTE: THERE IS NO MUCH ROOM ON THE REAR OF THE LOT. |
| | CLEARLY SHOW HOW RETAINING THE WATER IN THE REAR OF THE |
| | LOT WITHOUT DUMPING INTO THE NEIGHBOR'S PROPERTY. |
| | |
| | 2- THE ADDRESS OF THE JOB SHOWN ON PLANS IS INCOMPLETE. |
| | ALL PLANS NEED TO HAVE THE COMPLETE ADDRESS OF THE |
| | PROPOSED HOUSE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | A) THE BUILDING OWNER, THE ARCHITECT OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE BOTTOM OF THE FORM THAT THE BUILDING IS |
| | IN COMPLIANCE WITH THE CODE PRIOR TO RECEIVING THE |
| | PERMIT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING PROJECT ADDRESS, BUILDER'S NAME, PERMIT |
| | OFFICE, JURISDICTION, ETC. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) PROVIDE THE NAME OF THE PERSON DOING THE |
| | CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) ACCORDING TO PROJECT INFORMATION ON TOP OF PAGE 2 OF |
| | 4, THE HOUSE WAS ROTATED 180 DEGREES. CLARIFY WHY ITEM |
| | #5 ON PAGE 1 OF 4 STATES THAT THIS IS NOT A WORST CASE |
| | SCENARIO AND THEN THE HOUSE IS ROTATED 180 DEGREES?. |
| | CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION |
| | OF THE HOUSE AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. REVISE CALCULATIONS AS REQUIRED. |
| | |
| | E)WINDOW AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| | INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO |
| | MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $196,950. THE |
| | PERMIT FEE BALANCE IS $3937.32. |
| | |
| | 5- OWNER IS APPLYING FOR AN OWNER/BUILDER PERMIT UNDER |
| | THE SECTION 489.103 FLORIDA STATUTES. ACCORDING TO |
| | PROPERTY APPRAISER RECORDS, THE OWNER ALSO OWN OTHER 6 |
| | HOUSES/PROPERTIES. PLEASE CLARIFY PURPOSE OF THE |
| | CONSTRUCTION OF THIS HOUSE FOR THE RECORDS. A LICENSED |
| | CONTRACTOR MAY BE REQUIRED IF THE HOUSE IS GOING TO BE |
| | SOLD OR RENTED WITHIN ONE YEAR AFTER THE CONSTRUCTION |
| | IS COMPLETE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |