 PLUMBING COMMENTS:
  
 1. SHT. CHLS-0.1.1 THE RESTROOM FIXTURE COUNT IS
 CALLING OUT A TOTAL OF 10 TOILETS FOR WOMEN BUT I ONLY
 COUNT 9 ON THE PLAN PLEASE CLARIFY 10 IS THE REQUIRED
 NUMBER. PER FBC PL TABLE 403.1 AND WPB AMEND TO FBC
 107.2.1
  
 2. SHT. CH-5.3 SHOW CLEAR FLOOR SPACE FOR THE TOILET
 AND WATER FOUNTAIN FOR FORWARD APPROACH. PER FBC ACC
 604.3.1, 602.2
  
 3. SHT. CH-5.3 THE ACCESSIBILITY NOTE ARE CALLING OUT
 FAC 2014 5TH EDITION THE COMPLIANT CODE SHALL BE FBC
 ACC 1017 6TH EDITION. WPB AMEND TO FBC 107.2.1
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. FBC ACC 609.4
  
 5. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. FBC
 ACC 604.5.1
  
 6. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. FBC ACC 604.5.2
  
 7. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. FBC ACC 603.3
  
 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. FBC ACC 604.7
  
 9. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION. FBC ACC 604.4
  
 10. ON THE FLOOR PLANS THE SANITARY PIPING IS SHOWN AS
 A DASHED LINE THE PLUMBING LEGEN SHWS A DASHED LINE AS
 A VENT PLEAS CLARIFY AND LABEL ALL PIPING. PER WPB
 AMEND TO FBC 107.2.1
  
 11. SHT. P-3.0 PLEASE LABEL ENLARGE ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P-3.0.1, 3.1.1, P-3.1 P3.0 LABEL THE ENDS OF
 THE PIPE TO MATCH UP TO OTHER END WPB AMED TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  