| Date |
Text |
| 2019-05-16 12:58:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040465 |
| | 5/16/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER |
| | HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17 |
| | ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS |
| | OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS |
| | C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| | COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| | FINAL INSPECTION. |
| | |
| | 2) SHEETS M2.0, M2.1, & M2.2: THE AC CALCULATIONS FOR |
| | AHU-1 INDICATE AN AIRFLOW OF 1316 CFMS FOR THE GAME |
| | ROOM, HOWEVER THE EQUIPMENT SCHEDULE INDICATES 2400 |
| | CFMS- PLEASE CLARIFY THIS INCONSISTENCY. PLEASE NOTE |
| | THAT THE PLAN SHOWS 1470 CFMS FOR THE GAME ROOM AND 375 |
| | CFMS FOR THE TOILET ROOMS TOTALING 1845 CFMS FOR AHU-1. |
| | IN ADDITION, THE CALCS INDICATE AN AIRFLOW OF 1937 CFMS |
| | FOR AHU-8 AND THE SCHEDULE INDICATES 3000. |
| | |
| | 3) M2.0: THE O/A CALCULATIONS (FBC MINIMUM VENTILATION |
| | RATES) FOR AHU-3 (DINING & LOUNGE) ARE NOT IN |
| | COMPLIANCE WITH TABLE 403.3.1.1 FBC M. |
| | RATES FOR DINING ROOMS ARE BASED ON 70 PERSONS PER 1000 |
| | SF. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SF. |
| | RATES FOR LOUNGES ARE BASED ON 100 PERSONS PER 1000 SF. |
| | AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SF. |
| | |
| | 4) M2.1, M2.2 CH-0.1.1: FIRE DAMPERS ARE MISSING FOR |
| | THE MAIN AC DUCTS PENETRATING THE 1HR. FIRE-RATED AC |
| | CLOSET WALLS- SECTION 607.5.3 FBC M. |
| | |
| | 5) M2.1: THE O/A INTAKE OPENING FOR AHU-3 APPEARS TO BE |
| | WITHIN 10' TO THE EXHAUST OUTLET FOR EF-5- SECTION |
| | 401.4 FBC M. |
| | |
| | 6) M2.0 & M2.1: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR EF-4 AND EF-5- TABLE 403.3.1.1 FBC M. |
| | |
| | 7) M2.1: PROVIDE EQUIPMENT PLANS AND EQUIPMENT |
| | SCHEDULES FOR THE CATERING KITCHEN AND THE BACK OF |
| | HOUSE. PROVIDE PRODUCT DATA SHEETS FOR ALL COOKING |
| | APPLIANCES- SECTION 107.2.1 FBC M. |
| | |
| | 8) M2.2: THE O/A LOUVER FOR AHU-5 IS MISLABELED AS AN |
| | EXHAUST LOUVER- PLEASE CORRECT. |
| | |
| | 9) M-3.0: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE NEW CONDENSER PADS AND MOUNTING OF |
| | THE CONDENSERS- SEE SECTION 301.15 FBC M, AND SECTION |
| | 1609 FBC B. |
| | A) PROVIDE CONSTRUCTION DETAILS FOR THE PAD. B) THE |
| | MIAMI-DADE NOA #16-0712.07 LISTED IN THE CONDENSING |
| | UNIT DETAIL IS APPLICABLE FOR RHEEM UNITS ONLY- TRANE |
| | UNITS ARE SHOWN IN THE SCHEDULE. |
| | |
| | 10) SUBMIT THE FL. PRODUCT APPROVAL AND/OR THE MIAMI |
| | DADE NOA FOR THE O/A INLET AND EXHAUST LOUVERS- RULE |
| | 9N-3 FAC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |