Plan Review Notes
Plan Review Notes For Permit 19040465
Permit Number 19040465
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-16 12:58:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040465
 5/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER
 HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17
 ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS
 OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS
 C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION.
  
 2) SHEETS M2.0, M2.1, & M2.2: THE AC CALCULATIONS FOR
 AHU-1 INDICATE AN AIRFLOW OF 1316 CFMS FOR THE GAME
 ROOM, HOWEVER THE EQUIPMENT SCHEDULE INDICATES 2400
 CFMS- PLEASE CLARIFY THIS INCONSISTENCY. PLEASE NOTE
 THAT THE PLAN SHOWS 1470 CFMS FOR THE GAME ROOM AND 375
 CFMS FOR THE TOILET ROOMS TOTALING 1845 CFMS FOR AHU-1.
 IN ADDITION, THE CALCS INDICATE AN AIRFLOW OF 1937 CFMS
 FOR AHU-8 AND THE SCHEDULE INDICATES 3000.
  
 3) M2.0: THE O/A CALCULATIONS (FBC MINIMUM VENTILATION
 RATES) FOR AHU-3 (DINING & LOUNGE) ARE NOT IN
 COMPLIANCE WITH TABLE 403.3.1.1 FBC M.
 RATES FOR DINING ROOMS ARE BASED ON 70 PERSONS PER 1000
 SF. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SF.
 RATES FOR LOUNGES ARE BASED ON 100 PERSONS PER 1000 SF.
 AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SF.
  
 4) M2.1, M2.2 CH-0.1.1: FIRE DAMPERS ARE MISSING FOR
 THE MAIN AC DUCTS PENETRATING THE 1HR. FIRE-RATED AC
 CLOSET WALLS- SECTION 607.5.3 FBC M.
  
 5) M2.1: THE O/A INTAKE OPENING FOR AHU-3 APPEARS TO BE
 WITHIN 10' TO THE EXHAUST OUTLET FOR EF-5- SECTION
 401.4 FBC M.
  
 6) M2.0 & M2.1: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR EF-4 AND EF-5- TABLE 403.3.1.1 FBC M.
  
 7) M2.1: PROVIDE EQUIPMENT PLANS AND EQUIPMENT
 SCHEDULES FOR THE CATERING KITCHEN AND THE BACK OF
 HOUSE. PROVIDE PRODUCT DATA SHEETS FOR ALL COOKING
 APPLIANCES- SECTION 107.2.1 FBC M.
  
 8) M2.2: THE O/A LOUVER FOR AHU-5 IS MISLABELED AS AN
 EXHAUST LOUVER- PLEASE CORRECT.
  
 9) M-3.0: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE NEW CONDENSER PADS AND MOUNTING OF
 THE CONDENSERS- SEE SECTION 301.15 FBC M, AND SECTION
 1609 FBC B.
 A) PROVIDE CONSTRUCTION DETAILS FOR THE PAD. B) THE
 MIAMI-DADE NOA #16-0712.07 LISTED IN THE CONDENSING
 UNIT DETAIL IS APPLICABLE FOR RHEEM UNITS ONLY- TRANE
 UNITS ARE SHOWN IN THE SCHEDULE.
  
 10) SUBMIT THE FL. PRODUCT APPROVAL AND/OR THE MIAMI
 DADE NOA FOR THE O/A INLET AND EXHAUST LOUVERS- RULE
 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER