| 2019-04-24 13:44:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A OCH - UNDER THE FIRE SPRINKLER AND FIRE |
| | ALARM, NO INFORMATION IS INDICATED. |
| | |
| | PER NFPA 101, CHAPTER 12, ASSEMBLY OCCUPANCIES, A FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM IS REQUIRED. |
| | |
| | PLEASE PROVIDE THE APPLICABLE INFORMATION IN THIS AREA. |
| | |
| | |
| | |
| | 2) SHEET C 6 00 - A FIRE MAIN WITH A FDC IS INDICATED |
| | AS GOING INTO THE BUILDING. |
| | |
| | PER # 1 ABOVE PLEASE INDICATE THE APPLIOCABLE |
| | INFORMATION AS REQUIRED. |
| | |
| | |
| | |
| | 3) FIRE SPRINKLER SYSTEMS ARE REQUIRED TO HAVE F.A.C. |
| | 61G INFORMATION AND SUBMITTED WITH THIS MASTER PERMIT. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| | DOCUMENTS. |
| | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S |
| | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS |
| | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A |
| | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND |
| | EXPERIENCE. |
| | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY |
| | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH |
| | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS |
| | ARE INTENDED TO CONFORM TO. |
| | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF |
| | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF |
| | THE SYSTEM. |
| | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT |
| | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING |
| | DOCUMENTS. |
| | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY |
| | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE |
| | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE |
| | STATED PURPOSE OF THESE RESPONSIBILITY RULES. |
| | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING |
| | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR |
| | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE |
| | OF SUCH DOCUMENTS. |
| | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN |
| | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR |
| | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO |
| | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER |
| | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS |
| | RESPONSIBILITY. |
| | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY |
| | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST |
| | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. |
| | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY |
| | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN |
| | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC |
| | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND |
| | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE |
| | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES |
| | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE |
| | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A |
| | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR |
| | AGENCY APPROVAL ACTION ON THE SAME PROJECT. |
| | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW |
| | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW |
| | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. |
| | |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | PLEASE PROVIDE THE REQUIRED INFORMATION IN PLAN SETS |
| | DRAWINGS OR IN NARRATIVE FORM SIGNED AND SEALED BY THE |
| | EOR. |
| | |
| | |
| | |
| | 4) SHEET C 6 00 - THERE IS UNDERGROUND FIRE LINE |
| | INDICATED. |
| | |
| | ALL FIRE LINE UNDERGROUND SHALL BE DONE UNDER SEPARATE |
| | SHOP DRAWINGS BY CERTIFIED STATE OF FLORIDA UNDERGROUND |
| | CONTRACTORS IN COMPLIANCE WITH NFPA 24. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 5) SHEET 2.1 - THERE ARE NO INDICATIONS OF EXIT SIGNS |
| | IN THE MAILRROM, AT THE CLUB ROOM SIDE OF STAIR # 1 |
| | DOOR, THE INTERIOR EXIT DOOR OF STAIR # 1 EXIT DOOR, |
| | INTERIOR EXIDOOR STAIR # 2, GAME ROOM DOOR # 7, |
| | CATERING KITHEN EXIT DOOR, OR ANY DIRECTIONAL EXIT |
| | MARKING IN THE COOMON AREAS. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS |
| | NOT READILY APPARENT TO THE OCCUPANTS. |
| | |
| | 7.10.2 DIRECTIONAL SIGNS. |
| | 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A |
| | DIRECTIONAL |
| | INDICATOR SHOWING THE DIRECTION OF TRAVEL, SHALL BE |
| | PLACED IN EVERY |
| | LOCATION WHERE THE DIRECTION OF TRAVEL TO REACH THE |
| | NEAREST EXIT IS |
| | NOT APPARENT. |
| | |
| | PLEASE REVIEW AND PROVIDE REQUIRED EXIT SIGNANGE AS |
| | REQUIRED. |
| | |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF TACTILE EXIT MARKINGS |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE |
| | SHALL BE |
| | PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS |
| | OTHERWISE |
| | PROVIDED IN 7.10.1.4: |
| | (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR |
| | REQUIRING AN |
| | EXIT SIGN. |
| | (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. |
| | (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, |
| | AMERICAN |
| | NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS |
| | AND |
| | FACILITIES. |
| | |
| | PLEASE PROVIDE A APPLICABLE NOTE OF ACKNOWLEDGEMENT AS |
| | ENSURE INSTALLATION AS REQUIRED. |
| | |
| | |
| | |
| | 7) SHEET E 2.1A - THERE ARE NO INDICATIONS OF ANY EXIT |
| | SIGNAGE. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS |
| | NOT READILY APPARENT TO THE OCCUPANTS. |
| | |
| | 7.10.2 DIRECTIONAL SIGNS. |
| | 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A |
| | DIRECTIONAL |
| | INDICATOR SHOWING THE DIRECTION OF TRAVEL, SHALL BE |
| | PLACED IN EVERY |
| | LOCATION WHERE THE DIRECTION OF TRAVEL TO REACH THE |
| | NEAREST EXIT IS |
| | NOT APPARENT. |
| | |
| | PLEASE REVIEW AND PROVIDE REQUIRED EXIT SIGNANGE AS |
| | REQUIRED. |
| | |
| | |
| | |
| | 8) SHEET E 2.0 & 2.2 - THERE ARE INDICATIONS OF FIRE |
| | ALRM EQUIPMENT. |
| | |
| | ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE |
| | ALARM CONTRATORS. |
| | |
| | PLEASE PROVIDE A APPLICABLE NOTE OF ACKNOWLEDGEMENT AS |
| | ENSURE INSTALLATION AS REQUIRED. |
| | |
| | |
| | |
| | 9) THE FACP COULD NOT BE LOCATED. |
| | |
| | IS THERE A PROPOSED LOCATION PRIOR TO SUBMITTING FA |
| | SHOP DRAWINGS? |
| | |
| | PLEASE PROVIDE IF APPLICABLE. |
| | |
| | |
| | |
| | 10) SHEET CHLS 0 1.1 - THERE IS AN INDICATION OF A |
| | DIAGANOL REMOTE DISTANCE LINE SHOWING A DISTANCE |
| | DIVIDED BY 2. |
| | |
| | IF THIS IS A SPRINKLERED BUILDING(IT IS REQUIRED) THE |
| | DISTANCE IS DIVIDED BY 3. (THE 2ND FLOOR PLAN DOES |
| | INDICATE IT CORRECTLY) |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.7, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS, |
| | EXIT |
| | ACCESSES, OR EXIT DISCHARGES, MEASURED IN ACCORDANCE |
| | WITH 7.5.1.3.2, |
| | SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE |
| | MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE |
| | SERVED. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 11) SHEET CH 5.1 - THERE ARE NO INDICATIONS OF PANIC |
| | HARDWARE ON ANY DOOR IN THE DOOR SCHEDULE. |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 12) THERE ARE INDICATIONS OF AN ELEVATOR |
| | |
| | PER NFPA CH 12 |
| | |
| | 12.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. ELEVATORS, |
| | ESCALATORS, AND CONVEYORS SHALL COMPLY WITH THE |
| | PROVISIONS OF |
| | SECTION 9.4. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |