| 2019-05-31 09:59:06 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19040465 |
| | REVIEWED: MAY 31, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1. ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN |
| | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW |
| | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE |
| | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR |
| | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS |
| | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION |
| | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, |
| | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR |
| | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL |
| | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED |
| | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS |
| | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE |
| | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN |
| | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW |
| | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED |
| | DEVELOPMENTS. |
| | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. |
| | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES |
| | COORDINATOR 822-1515 E-MAIL: [email protected] |
| | |
| | 2. F.S. 553.79(5) THRESHOLD BUILDING. |
| | THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD |
| | BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO |
| | COMMENCEMENT. |
| | A) COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| | CONTRACTOR. IF PDF OF AGREEMENT IS NEEDED PLEASE |
| | CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL |
| | PROVIDE VIA E-MAIL. |
| | B) PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| | PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL |
| | INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY |
| | PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO |
| | BE ON-SITE. |
| | C) ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT |
| | REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND |
| | CHAPTER 633.? |
| | D) THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). |
| | - THERE IS A SIMILAR STATEMENT LIKE ITEM C IN THE |
| | COMMENT ABOVE ON STRUCTURAL SHEETS, BUT IT NEEDS TO BE |
| | THE STATEMENT IN QUOTES FROM ITEM C ABOVE. ADD |
| | THRESHOLD INSPECTION PLAN. |
| | |
| | 3. 319 FBC[R] ADDRESS IS NEEDED FOR THIS LOT. THE |
| | PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN |
| | ASSIGNED TO THE PROPERTY. |
| | - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR |
| | BY E-MAIL [email protected] |
| | |
| | 4. 103.1.1.2 FBC[CE] CODE COMPLIANCE CERTIFICATION. THE |
| | BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | - HAVE THE RESPONSIBLE PARTIES SIGN THE ENERGY |
| | CALCULATIONS. |
| | |
| | 5. 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS |
| | SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | A. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, |
| | EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD. |
| | B. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | C. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| | OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | - WHICH METHOD OF COMPLIANCE IS BEING UTILIZED? PROVIDE |
| | DOCUMENTATION TO SHOW HOW IT IS BEING IMPLEMENTED. |
| | |
| | 6. 705.8.1 ALLOWABLE AREA OF OPENINGS. THE MAXIMUM AREA |
| | OF UNPROTECTED AND PROTECTED OPENINGS PERMITTED IN AN |
| | EXTERIOR WALL IN ANY STORY OF A BUILDING SHALL NOT |
| | EXCEED THE PERCENTAGES SPECIFIED IN TABLE 705.8. |
| | - VERIFY THAT OPENINGS ON THE LEFT ELEVATION ARE LESS |
| | THAN 25 PERCENT OF WALL AREA. |
| | |
| | 7. 228.2 FBC[A] MAIL BOXES. WHERE MAIL BOXES ARE |
| | PROVIDED IN AN INTERIOR LOCATION, AT LEAST 5 PERCENT, |
| | BUT NO FEWER THAN ONE, OF EACH TYPE SHALL COMPLY WITH |
| | 309. IN RESIDENTIAL FACILITIES, WHERE MAIL BOXES ARE |
| | PROVIDED FOR EACH RESIDENTIAL DWELLING UNIT, MAIL BOXES |
| | COMPLYING WITH 309 SHALL BE PROVIDED FOR EACH |
| | RESIDENTIAL DWELLING UNIT REQUIRED TO PROVIDE MOBILITY |
| | FEATURES COMPLYING WITH 809.2 THROUGH 809.4. |
| | - IS THIS THE MAILROOM THAT SERVES ALL RESIDENTIAL? |
| | |
| | 8. 308.2.1 FBC[A] UNOBSTRUCTED. WHERE A FORWARD REACH |
| | IS UNOBSTRUCTED, THE HIGH FORWARD REACH SHALL BE 48 |
| | INCHES (1220 MM) MAXIMUM AND THE LOW FORWARD REACH |
| | SHALL BE 15 INCHES (380 MM) MINIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | - PROVIDE DETAIL FOR REACH RANGE IN THE MAILROOM. |
| | |
| | 9. 804 FBC[A] KITCHENS AND KITCHENETTES. THROUGH |
| | KITCHEN OR U KITCHEN |
| | - PLEASE PROVIDE DETAILS FOR B.O.H., COFFEE BAR AND |
| | GALLEY KITCHEN. |
| | |
| | 10. 716.5 FBC TABLE[B] OPENING FIRE PROTECTION |
| | ASSEMBLIES, RATINGS AND MARKINGS |
| | - CHECK FIRE RATINGS FOR DOOR TYPE 3 FOR ENTRY INTO |
| | INTERIOR STAIRWAYS. ALSO, LOOK AT ALLOWABLE FOR GLASS |
| | TYPE SINCE THE DOOR TYPE STATES A 12X12 VISION PANEL |
| | WILL BE INCLUDED. |
| | |
| | 11. 906.1 FBC[B] WHERE REQUIRED. PORTABLE FIRE |
| | EXTINGUISHERS SHALL BE INSTALLED IN ALL OF THE |
| | FOLLOWING LOCATIONS: IN GROUP A, B, E, F, H, I, M, R-1, |
| | R-2, R-4 AND S OCCUPANCIES. |
| | - (SEE EXCEPTIONS AND REQUIREMENTS) I SEE SYMBOLS ON |
| | LIFE SAFETY KEY, BUT I DO NOT SEE ANY LOCATED ON PLANS. |
| | PLEASE SHOW LOCATIONS WHERE FIRE EXTINGUISHERS WILL BE |
| | INSTALLED, OR INDICATE WHAT PAGE THEY ARE ON. |
| | |
| | 12. 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| | - ADD TO SUPPORTING DOCUMENTS FILE IN PROJECTDOX. |
| | |
| | 13. 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS THAT |
| | WILL BE SUPPLIED AT A LATER DATE, OR INDICATE WHICH |
| | PAGE A LIST CAN BE FOUND. |
| | |
| | 14. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERED. |
| | - FOR TILE ROOF INCLUDE PRODUCT APROVAL FOR ATTACHMENT. |
| | |
| | 15. 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS |
| | TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | 16. 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B] |
| | LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND |
| | GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE |
| | IT DEFERRED. |
| | - |
| | |
| | 17. 806.3 FBC[B] COMBUSTIBLE DECORATIVE MATERIALS. IN |
| | OTHER THAN GROUP I-3, CURTAINS, DRAPERIES, FABRIC |
| | HANGINGS AND SIMILAR COMBUSTIBLE DECORATIVE MATERIALS |
| | SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH |
| | SECTION 806.4 AND SHALL NOT EXCEED 10 PERCENT OF THE |
| | SPECIFIC WALL OR CEILING AREA TO WHICH SUCH MATERIALS |
| | ARE ATTACHED. FIXED OR MOVABLE WALLS AND PARTITIONS, |
| | PANELING, WALL PADS AND CRASH PADS APPLIED STRUCTURALLY |
| | OR FOR DECORATION, ACOUSTICAL CORRECTION, SURFACE |
| | INSULATION OR OTHER PURPOSES SHALL BE CONSIDERED |
| | INTERIOR FINISH SHALL COMPLY WITH SECTION 803 AND SHALL |
| | NOT BE CONSIDERED DECORATIVE MATERIALS OR FURNISHINGS. |
| | (SEE EXCEPTIONS FOR 806.3) |
| | - IF APPLICABLE THIS CAN BE ADDED TO DEFERRED SUBMITTAL |
| | LIST. |
| | |
| | 18. 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND |
| | PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS |
| | NOT ADVERSELY AFFECTED BY MOISTURE. EXCEPTION: THIS |
| | SECTION DOES NOT APPLY TO THE FOLLOWING BUILDINGS AND |
| | SPACES: 1. DWELLING UNITS AND SLEEPING UNITS. 2. TOILET |
| | ROOMS THAT ARE NOT ACCESSIBLE TO THE PUBLIC AND THAT |
| | HAVE NOT MORE THAN ONE WATER CLOSET. ACCESSORIES SUCH |
| | AS GRAB BARS, TOWEL BARS, PAPER DISPENSERS AND SOAP |
| | DISHES, PROVIDED ON OR WITHIN WALLS, SHALL BE INSTALLED |
| | AND SEALED TO PROTECT STRUCTURAL ELEMENTS FROM |
| | MOISTURE. |
| | - NOTE 18 ON SHEET CH-5.1 CALLS FOR PUBLIC BATHROOMS TO |
| | HAVE SURFACE UP TO 5 FEET. CAN THIS NOTE BE ADDED TO |
| | SHEET CH-5.3 SINCE THE BATHROOM ELEVATIONS DON?T SHOW |
| | WALL MATERIAL? |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |