Plan Review Notes
Plan Review Notes For Permit 19040465
Permit Number 19040465
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-31 09:59:06****CORRECTIONS****
 W.P.B. PERMIT: 19040465
 REVIEWED: MAY 31, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 2. F.S. 553.79(5) THRESHOLD BUILDING.
 THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD
 BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO
 COMMENCEMENT.
 A) COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR. IF PDF OF AGREEMENT IS NEEDED PLEASE
 CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL
 PROVIDE VIA E-MAIL.
 B) PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL
 INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY
 PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO
 BE ON-SITE.
 C) ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.?
 D) THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
 - THERE IS A SIMILAR STATEMENT LIKE ITEM C IN THE
 COMMENT ABOVE ON STRUCTURAL SHEETS, BUT IT NEEDS TO BE
 THE STATEMENT IN QUOTES FROM ITEM C ABOVE. ADD
 THRESHOLD INSPECTION PLAN.
  
 3. 319 FBC[R] ADDRESS IS NEEDED FOR THIS LOT. THE
 PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY.
 - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR
 BY E-MAIL [email protected]
  
 4. 103.1.1.2 FBC[CE] CODE COMPLIANCE CERTIFICATION. THE
 BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
 - HAVE THE RESPONSIBLE PARTIES SIGN THE ENERGY
 CALCULATIONS.
  
 5. 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 A. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 B. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 C. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 - WHICH METHOD OF COMPLIANCE IS BEING UTILIZED? PROVIDE
 DOCUMENTATION TO SHOW HOW IT IS BEING IMPLEMENTED.
  
 6. 705.8.1 ALLOWABLE AREA OF OPENINGS. THE MAXIMUM AREA
 OF UNPROTECTED AND PROTECTED OPENINGS PERMITTED IN AN
 EXTERIOR WALL IN ANY STORY OF A BUILDING SHALL NOT
 EXCEED THE PERCENTAGES SPECIFIED IN TABLE 705.8.
 - VERIFY THAT OPENINGS ON THE LEFT ELEVATION ARE LESS
 THAN 25 PERCENT OF WALL AREA.
  
 7. 228.2 FBC[A] MAIL BOXES. WHERE MAIL BOXES ARE
 PROVIDED IN AN INTERIOR LOCATION, AT LEAST 5 PERCENT,
 BUT NO FEWER THAN ONE, OF EACH TYPE SHALL COMPLY WITH
 309. IN RESIDENTIAL FACILITIES, WHERE MAIL BOXES ARE
 PROVIDED FOR EACH RESIDENTIAL DWELLING UNIT, MAIL BOXES
 COMPLYING WITH 309 SHALL BE PROVIDED FOR EACH
 RESIDENTIAL DWELLING UNIT REQUIRED TO PROVIDE MOBILITY
 FEATURES COMPLYING WITH 809.2 THROUGH 809.4.
 - IS THIS THE MAILROOM THAT SERVES ALL RESIDENTIAL?
  
 8. 308.2.1 FBC[A] UNOBSTRUCTED. WHERE A FORWARD REACH
 IS UNOBSTRUCTED, THE HIGH FORWARD REACH SHALL BE 48
 INCHES (1220 MM) MAXIMUM AND THE LOW FORWARD REACH
 SHALL BE 15 INCHES (380 MM) MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 - PROVIDE DETAIL FOR REACH RANGE IN THE MAILROOM.
  
 9. 804 FBC[A] KITCHENS AND KITCHENETTES. THROUGH
 KITCHEN OR U KITCHEN
 - PLEASE PROVIDE DETAILS FOR B.O.H., COFFEE BAR AND
 GALLEY KITCHEN.
  
 10. 716.5 FBC TABLE[B] OPENING FIRE PROTECTION
 ASSEMBLIES, RATINGS AND MARKINGS
 - CHECK FIRE RATINGS FOR DOOR TYPE 3 FOR ENTRY INTO
 INTERIOR STAIRWAYS. ALSO, LOOK AT ALLOWABLE FOR GLASS
 TYPE SINCE THE DOOR TYPE STATES A 12X12 VISION PANEL
 WILL BE INCLUDED.
  
 11. 906.1 FBC[B] WHERE REQUIRED. PORTABLE FIRE
 EXTINGUISHERS SHALL BE INSTALLED IN ALL OF THE
 FOLLOWING LOCATIONS: IN GROUP A, B, E, F, H, I, M, R-1,
 R-2, R-4 AND S OCCUPANCIES.
 - (SEE EXCEPTIONS AND REQUIREMENTS) I SEE SYMBOLS ON
 LIFE SAFETY KEY, BUT I DO NOT SEE ANY LOCATED ON PLANS.
 PLEASE SHOW LOCATIONS WHERE FIRE EXTINGUISHERS WILL BE
 INSTALLED, OR INDICATE WHAT PAGE THEY ARE ON.
  
 12. 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 - ADD TO SUPPORTING DOCUMENTS FILE IN PROJECTDOX.
  
 13. 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS THAT
 WILL BE SUPPLIED AT A LATER DATE, OR INDICATE WHICH
 PAGE A LIST CAN BE FOUND.
  
 14. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
 - FOR TILE ROOF INCLUDE PRODUCT APROVAL FOR ATTACHMENT.
  
 15. 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS
 TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 16. 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B]
 LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND
 GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERRED.
 -
  
 17. 806.3 FBC[B] COMBUSTIBLE DECORATIVE MATERIALS. IN
 OTHER THAN GROUP I-3, CURTAINS, DRAPERIES, FABRIC
 HANGINGS AND SIMILAR COMBUSTIBLE DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH
 SECTION 806.4 AND SHALL NOT EXCEED 10 PERCENT OF THE
 SPECIFIC WALL OR CEILING AREA TO WHICH SUCH MATERIALS
 ARE ATTACHED. FIXED OR MOVABLE WALLS AND PARTITIONS,
 PANELING, WALL PADS AND CRASH PADS APPLIED STRUCTURALLY
 OR FOR DECORATION, ACOUSTICAL CORRECTION, SURFACE
 INSULATION OR OTHER PURPOSES SHALL BE CONSIDERED
 INTERIOR FINISH SHALL COMPLY WITH SECTION 803 AND SHALL
 NOT BE CONSIDERED DECORATIVE MATERIALS OR FURNISHINGS.
 (SEE EXCEPTIONS FOR 806.3)
 - IF APPLICABLE THIS CAN BE ADDED TO DEFERRED SUBMITTAL
 LIST.
  
 18. 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE. EXCEPTION: THIS
 SECTION DOES NOT APPLY TO THE FOLLOWING BUILDINGS AND
 SPACES: 1. DWELLING UNITS AND SLEEPING UNITS. 2. TOILET
 ROOMS THAT ARE NOT ACCESSIBLE TO THE PUBLIC AND THAT
 HAVE NOT MORE THAN ONE WATER CLOSET. ACCESSORIES SUCH
 AS GRAB BARS, TOWEL BARS, PAPER DISPENSERS AND SOAP
 DISHES, PROVIDED ON OR WITHIN WALLS, SHALL BE INSTALLED
 AND SEALED TO PROTECT STRUCTURAL ELEMENTS FROM
 MOISTURE.
 - NOTE 18 ON SHEET CH-5.1 CALLS FOR PUBLIC BATHROOMS TO
 HAVE SURFACE UP TO 5 FEET. CAN THIS NOTE BE ADDED TO
 SHEET CH-5.3 SINCE THE BATHROOM ELEVATIONS DON?T SHOW
 WALL MATERIAL?
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  