2019-07-11 09:25:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040464
 7/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS: THE
 SUBMITTED TRACE HEAT LOAD CALCULATIONS ARE NOT IN
 COMPLIANCE WITH SECTIONS C407.5.2.2 & C407.5.2.2 FBC EC
 BECAUSE ZONES HAVE NOT BEEN DEFINED. C407.5.2.3
 MULTIFAMILY RESIDENTIAL BUILDINGS.
 RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL
 BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME
 ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE
 THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR
 FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING
 THESE FEATURES.
  
 2) COMMENT #3 FROM THE 1ST REVIEW PARTIALLY EXISTS:
 PROVIDE THE SEQUENCE OF OPERATION FOR THE EXHAUST FAN
 IN THE STORAGE AND DOMESTIC PUMP ROOMS. A) THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FROM THE EXHAUST OUTLET
 TO OPERABLE OPENINGS AND GRADE NOT PROVIDED.
  
 3) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS: M5.1.1:
 PLEASE CORRECT THE FBC MINIMUM VENTILATION CALCULATIONS
 AND REMOVE OR CORRECT THE NOTES SPECIFYING RATES BASED
 ON THE TABLES IN THE FBC R, THE FBC R CODE IS
 APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES, AND
 TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED
 BELOW, AND INDICATE COMPLIANCE:
 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS.
 AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A
 MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION
 THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT.
 LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR
 DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER,
 ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR
 AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE
 REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE
 PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM
 CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH EQUATION 4-9.
 (EQUATION 4-9)
 WHERE:
 QOA = OUTDOOR AIRFLOW RATE, CFM
 AFLOOR = FLOOR AREA, FT2
 NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE
 EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT
 REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS
 CONTROLS THAT ENABLE OPERATION
 FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE
 AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD
 SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9.
  
 4) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS. PLEASE
 NOTE THAT ALL BEDROOM RETURN TRANSFERS FROM THE MASTER
 BEDROOM SUITES ARE UNDERSIZED WITH THE EXCEPTION OF
 UNIT C2 WHICH HAS (2) 16X6 TRANSFERS. M4.4.1, 4.4.2,
 4.4.3, 4.4.5, & 4.4.6: THE RETURN TRANSFER GRILLS AT
 THE MASTER BEDROOM SUITES ARE UNDERSIZED PER SECTION
 601.6(2) AND 601.6(3) FBC M. THE RETURNS MUST BE SIZED
 LARGE ENOUGH TO RETURN ALL AIR FROM THE SUITE AT 50 SQ.
 INCHES PER 100 CFMS OF SUPPLY AIR.
  
 5) COMMENT #10 FROM THE 1ST REVIEW STILL EXISTS:
 M7.4.2- AC CLOSET DETAIL: INDICATE THE TYPE AND SIZE OF
 CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS 307.2.1
 AND 602.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  